18.16
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Synchrophasors
Settings for Synchrophasors
Legacy Settings
The PMU provides the following legacy synchrophasor settings that can be
enabled by setting PMLEGCY = Y.
PMSTN and PMID
Defines the name and number of the PMU. The PMSTN setting is an ASCII string
with as many as 16 characters. The PMID setting is a numeric value (1–65534). Use
your utility or synchrophasor data concentrator naming convention to determine
these settings.
PHVOLT and PHDATAV
PHDATAV and PHVOLT select which voltage synchrophasors to include in the
data packet. If MFRMT = FM, the only options available are V1 and ALL.
➤
PHDATAV := V1 will transmit only positive-sequence voltage,V1
➤
PHDATAV = PH will transmit phase voltages only (VA, VB, VC)
➤
PHDATAV := ALL will transmit V1, VA, VB, and VC
➤
PHDATAV := NA will not transmit any voltages
PHVOLT selects the voltage sources for the synchrophasor data selected by PHDATAV.
Use the PHVOLT setting to select any combination of available voltage terminals.
PHCURR and PHDATAI
PHDATAI and PHCURR select which current synchrophasors to include in the
data packet.
➤
PHDATAI := I1 will transmit only positive-sequence current, I1
➤
PHDATAI := PH transmits phase currents (IA, IB, IC)
➤
PHDATAI := ALL will transmit I1, IA, IB, and IC
➤
PHDATAI := NA will not transmit any currents
PHCURR selects the source current(s) for the synchrophasor data selected by
PHDATAI.
Use the PHCURR setting to select any combination of available current termi-
nals. If MFRMT = FM, only a single terminal can be selected.
PHNR
Selects the numerical representation of voltage and current phasor data in the
synchrophasor data stream. If MFRMT = FM, this setting is forced to F, a float-
ing point value.
PHFMT
Selects the phasor representation of voltage and current phasor data in the syn-
chrophasor data stream. If MFRMT = FM, this setting is forced to P, for polar
phasor format. This setting is hidden if PHDATAV and PHDATAI = NA.
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...