5.37
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Control
Bay Control Example Application
Enter bus-name labels (as many as ten characters) that describe each bus in the
one-line diagram.
The actual number of characters accepted depends on the pixel width of the string.
BUSNAM1 :=
Bus T
BUSNAM2 :=
Bus 2
BUSNAM3 :=
Bus 1
Breaker Information
The relay displays breaker information for as many as three breakers. For the bay
configuration in this example, the relay displays one. If more breakers were sup-
ported, based on the MIMIC setting selected, the settings associated with addi-
tional breakers would follow Breaker 1 settings.
Breaker Name Label
Enter a breaker name (as many as six characters) that describes each circuit
breaker in the one-line diagram.
The actual number of characters accepted depends on pixel width of the string.
B1HMINM :=
Bkr 1
Breaker Status
This SEL
OGIC
control equation reports breaker close status and breaker alarm
status. Any bit in the Relay Word can be programmed into this SEL
OGIC
control
equation, as well as logical operators. The equations below return the state of the
Bkr 1 status and any Bkr 1 alarm conditions.
521CLSM :=
52ACL1
521_ALM :=
52AAL1
Disconnect Information
The relay provides disconnect switch information for as many as ten disconnect
switches. For the bay configuration selected in this example, the relay supports
five disconnect switches.
Disconnect Name Label
Enter disconnect labels of as many as six characters in length that describe each
disconnect switch in the one-line diagram. The actual number of characters
accepted depends on pixel width of the string.
D01HMIN :=
Dis 1
Disconnect Status
Wire the normally open and normally closed auxiliary contacts from the discon-
nect switch to relay inputs, and program the relay inputs into 89AM01 and
89BM01 SEL
OGIC
control equations. These equations report the state of the dis-
connect switch auxiliary contacts. Both equations must be programmed for the
Disconnect Switch Status and Alarm Logic to function correctly.
89AM01 :=
IN103
89BM01 :=
IN104
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...