18.13
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Synchrophasors
Settings for Synchrophasors
PROTO
Setting this to PMU enables synchrophasor data transmission on the specific
serial port. Once set to PMU that specific serial port cannot be used for accessing
settings or issuing any ASCII commands.
If PROTO := PMU and MFRMT := C37.118, then the serial port will only
respond to C37.118 commands.
➤
Stop synchrophasor data
➤
Start synchrophasor data
➤
Send header data
➤
Send Configuration 1 data
➤
Send Configuration 2 data
➤
Process extended frame data
If PROTO := PMU or SEL and MFRMT := FM, then the serial port will only
respond to SEL Fast Message synchrophasor commands.
SPEED
Select the data rate (300–57600) for synchrophasor data transmission on the spe-
cific serial port. This setting affects the synchrophasor data packet size. See
munications Bandwidth on page 18.24
for detailed information.
PMUMODE
Set PMUMODE := SERVER if the serial port is intended to send synchrophasor
data. Client applications are described in
Real-Time Control on page 18.36
PMODC
NOTE:
If PMODC is set to a number
that exceeds the setting for
NUMPHDC, the port sends the data for
the first PMU configuration.
Select the data configuration (1-NUMPHDC) for synchrophasor data transmis-
sion on the specific serial port. This setting affects the synchrophasor data packet
size. See
Communications Bandwidth on page 18.24
for detailed information.
Through the use of this setting each serial port can be configured to stream
unique synchrophasor data.
EPMU := N Supersedes Synchrophasor Port Settings
The PROTO := PMU settings choice can be made even when Global setting
EPMU := N. However, in this situation, the serial port will not respond to any
commands or requests. Either enable synchrophasors by setting EPMU to Y, or
change the port PROTO setting to SEL.
If you use a computer terminal session or
AC
SEL
ERATOR
QuickSet SEL-5030
Software connected to a serial port, and then set that same serial port PROTO set-
ting to PMU, you will lose the ability to communicate with the relay through
ASCII commands or virtual file interface commands. If this happens, either con-
nect via another serial port (that has PROTO := SEL) or use the front-panel
HMI
SET/SHOW
screen to change the disabled port PROTO setting back to SEL.
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...