![Schweitzer Engineering Laboratories SEL-421-4 Скачать руководство пользователя страница 254](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726254.webp)
5.94
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Functions
Instantaneous Line Overcurrent Elements
Each of the instantaneous directional elements includes a torque control setting
(67P
n
TC, 67Q
n
TC, 67G
n
TC, where
n
= 1–4) to supervise the element operation.
The enable settings (E50P, E50Q, E50G) control how many of each type of
instantaneous/definite-time overcurrent elements are available. For example, if
E50P := 2, only 50P1, 67P1, 67P1T, 50P2, 67P2, and 67P2T are processed. The
remaining phase instantaneous/definite-time overcurrent elements (
n
= 3–4) are
defeated, and the output Relay Word bits are forced to logical 0.
Table 5.55
Phase Overcurrent Element Settings
Setting
Prompt
Range
Default (5 A)
Phase Instantaneous Overcurrent Elements
E50P
Phase Inst./Def.-Time O/C Elements
N, 1–4
1
50P1P
Level 1 Pickup (A)
OFF, (0.05–20) • I
NOM
10.00
50P2P
Level 2 Pickup (A)
OFF, (0.05–20) • I
NOM
OFF
50P3P
Level 3 Pickup (A)
OFF, (0.05–20) • I
NOM
OFF
50P4P
Level 4 Pickup (A)
OFF, (0.05–20) • I
NOM
OFF
Phase Definite-Time Overcurrent Elements
67P1D
Level 1 Time Delay (cycles)
0.000–16000
0.000
67P2D
Level 2 Time Delay (cycles)
0.000–16000
0.000
67P3D
Level 3 Time Delay (cycles)
0.000–16000
0.000
67P4D
Level 4 Time Delay (cycles)
0.000–16000
0.000
67P1TC
Level 1 Torque Control
SEL
OGIC
Equation
1
67P2TC
Level 2 Torque Control
SEL
OGIC
Equation
1
67P3TC
Level 3 Torque Control
SEL
OGIC
Equation
1
67P4TC
Level 4 Torque Control
SEL
OGIC
Equation
1
Table 5.56
Negative-Sequence Overcurrent Element Settings
Setting
Prompt
Range
Default
(5 A)
Negative-Sequence Instantaneous Overcurrent Elements
E50Q
Neg.-Seq. Inst./Def.-Time O/C Elements
N, 1–4
N
50Q1P
Level 1 Pickup (A)
OFF, (0.05–20) • I
NOM
OFF
50Q2P
Level 2 Pickup (A)
OFF, (0.05–20) • I
NOM
OFF
50Q3P
Level 3 Pickup (A)
OFF, (0.05–20) • I
NOM
OFF
50Q4P
Level 4 Pickup (A)
OFF, (0.05–20) • I
NOM
OFF
Negative-Sequence Definite-Time Overcurrent Elements
67Q1D
Level 1 Time Delay (cycles)
0.000–16000
0.000
67Q2D
Level 2 Time Delay (cycles)
0.000–16000
0.000
67Q3D
Level 3 Time Delay (cycles)
0.000–16000
0.000
67Q4D
Level 4 Time Delay (cycles)
0.000–16000
0.000
67Q1TC
Level 1 Torque Control
SEL
OGIC
Equation
1
67Q2TC
Level 2 Torque Control
SEL
OGIC
Equation
1
67Q3TC
Level 3 Torque Control
SEL
OGIC
Equation
1
67Q4TC
Level 4 Torque Control
SEL
OGIC
Equation
1
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...