9.6
SEL-421 Relay
Instruction Manual
Date Code 20171021
ASCII Command Reference
Description of Commands
SET
SET on page 14.48 in the SEL-400 Series Relays Instruction Manual
. The
following table lists the options specifically available in the SEL-421.
NOTE:
The SEL-421-4 has only one
100-line block of automation freeform
SEL
OGIC
control equation
programming.
Table 9.6
SET Command Overview
Command
Description
Access Level
SET
a
a
Parameter
n
= 1–6, representing Group 1 through Group 6.
Set the Group relay settings, beginning at the first setting
in the active group.
P, 2
SET
n
a
Set the Group
n
relay settings, beginning at the first set-
ting
n
each.
P, 2
SET A
b
b
Parameter
m
= 1–10 for Block 1 through Block 10.
Set the Automation SEL
OGIC
control equation relay set-
tings in Block 1.
A, 2
SET A
m
b
Set the Automation SEL
OGIC
control equation relay set-
tings in Block
m
.
A, 2
SET B
Bay control settings, beginning at the first setting in this
class.
P, A, O, 2
SET D
Set the DNP3 remapping settings, beginning at the first
setting in this class for instance 1.
P, A, O, 2
SET D
instance
Set the DNP3 remapping settings beginning at the first
setting of
instance
.
P, A, O, 2
SET F
Set the front-panel relay settings, beginning at the first set-
ting in this class.
P, A, O, 2
SET G
Set the Global relay settings, beginning at the first setting
in this class.
P, A, O, 2
SET L
a
Set the Protection SEL
OGIC
control equation relay settings
for the active settings group.
P, 2
SET L
n
a
Set the Protection SEL
OGIC
relay settings for Instance
n
,
which is Group
n
.
P, 2
SET M
Set the Breaker Monitor relay settings, beginning at the
first setting in this class.
P, 2
SET N
Enter text using the text-edit format.
P, A, O, 2
SET O
Set the Output SEL
OGIC
control equation relay settings,
beginning at OUT101.
O, 2
SET P
c
c
Parameter
p
= 1–3, F, or 5, corresponding to PORT 1–PORT 3, PORT F, or PORT 5.
Set the port presently in use, beginning at the first setting
for this port.
P, A, O, 2
SET P
p
c
Set the communications Port relay settings for Port
p
,
beginning at the first setting for this port.
P, A, O, 2
SET R
Set the Report relay settings, beginning at the first setting
for this class.
P, A, O, 2
SET T
Set the alias settings.
P, A, O, 2
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...