13.15
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
SEL
OGIC
Control Equation Programming
SEL
OGIC
Control Equation Elements
Evaluation of the latch bit value occurs at the end of the protection SEL
OGIC
con-
trol equation execution cycle. The values evaluated for Reset (PLT
nn
R) and Set
(PLT
nn
S) during SEL
OGIC
control equation execution remain unchanged until
after the evaluation of all SEL
OGIC
control equations, when the relay evaluates
the latch bit value (PLT
nn
). For example, if you have multiple SEL
OGIC
control
equations for set, the last equation in the protection freeform area dominates, and
the relay uses this equation to evaluate the latch.
Automation Latch Bits
The automation latch bits, ALT01–ALT32, are available in automation freeform
settings. Write freeform SEL
OGIC
control equations to set and reset these bits. As
with protection latch bits, the relay stores automation latch bits in nonvolatile
memory and preserves these through a relay power cycle and group change oper-
ations. With protection latch bits, you can implement Set and Reset programming
for each protection settings group. Automation SEL
OGIC
control equation pro-
gramming, however, has only one programming area active for all protection set-
tings groups.
The relay evaluates the latch bit value at the end of the automation freeform
SEL
OGIC
control equation execution cycle. The values for Reset (ALT
nn
R) and
Set (ALT
nn
S) remain unchanged until evaluation of all SEL
OGIC
control equa-
tions, when the relay evaluates the latch (ALT
nn
). For example, if you have mul-
tiple SEL
OGIC
control equations for set, the last equation in the automation
freeform area dominates, and the relay uses this equation to evaluate the latch.
Conditioning Timers
Use conditioning timers to condition Boolean values. Conditioning timers either
stretch incoming pulses or allow you to require that an input take a state for a cer-
tain period before reacting to the new state. Conditioning timers are available in
the protection freeform area, as shown in
. Conditioning timers have
the three input parameters and one output shown in
➤
In group settings, PLT04 supervises close and reclose
conditions:
➢
Autoreclose enable
E3PR1 := PLT02
AND PLT04
➢
Autoreclose drive-to-lockout
79DTL := NOT (PLT02
AND PLT04
) AND (3PT OR NOT
52AA1)
➢
Manual close
BK1MCL := (CC1 OR PB7_PUL)
AND PLT04
The above settings allow the HOT LINE TAG operator control pushbutton to
enable or disable close operations in the SEL-451. Any changes to these fac-
tory settings should be carefully designed and tested to ensure proper opera-
tion.
Example 13.6
Protection Latch Bits (Continued)
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...