8.26
SEL-421 Relay
Instruction Manual
Date Code 20171021
Settings
Group Settings
Make
settings if any of the Group settings E21P, E21G, E21XG, E50P,
E50G or E50Q := 3, 4, or 5.
Table 8.64
Zone/Level Direction
Setting
Prompt
Default Value
DIR3
Zone/Level 3 Directional Control (F, R)
R
DIR4
Zone/Level 4 Directional Control (F, R)
F
DIR5
Zone/Level 5 Directional Control (F, R)
F
Table 8.65
Directional Control Element
Setting
Prompt
Default Value
Increment
5 A
1 A
ORDER Ground Directional Element Priority
(combine Q, V, I)
QV
QV
50FP
a
a
Setting only available when Group setting E32 := Y. Setting automatically calculated when
E32 := AUTO or AUTO2.
Forward Directional Overcurrent Pickup
(0.25–5 A secondary) 5 A
(0.05–1 A secondary) 1 A
0.50
0.10
0.01
50RP
Reverse Directional Overcurrent Pickup
(0.25–5 A secondary) 5 A
(0.05–1 A secondary) 1 A
0.25
0.05
0.01
Z2F
Forward Directional Z2 Threshold
(–64.00 to +64.00
secondary) 5 A
(–320.00 to +320.00
secondary) 1 A
–0.30
–1.50
0.01
Z2R
Reverse Directional Z2 Threshold
(–64.00 to +64.00
secondary) 5 A
(–320.00 to +320.00
secondary) 1 A
0.30
1.50
0.01
a2
Positive-Sequence Restraint Factor, I2/I1
(0.02–0.50)
0.10
0.10
0.01
Zero-Sequence Restraint Factor, I2/I0 (0.10–1.20)
0.20
0.20
0.01
Z0F
Forward Directional Z0 Threshold
(–64.00 to +64.00
secondary) 5 A
(–320.00 to +320.00
secondary) 1 A
–0.30
–1.50
0.01
Z0R
Reverse Directional Z0 Threshold
(–64.00 to +64.00
secondary) 5 A
(–320.00 to +320.00
secondary) 1 A
0.30
1.50
0.01
a0
Positive-Sequence Restraint Factor, I0/I1 (0.02–0.5) 0.10
0.10
0.01
E32IV
Zero-Sequence Voltage and Current Enable
(SEL
OGIC
Equation)
1
1
Table 8.66
Pole-Open Detection
Setting
Prompt
Default Value Increment
EPO
Pole Open Detection (52, V)
52
27PO
Undervoltage Pole Open Threshold (1–200 V)
40
1
SPOD
Single Pole Open Dropout Delay (0.000–60 cycles) 0.500
0.125
3POD
Three Pole Open Dropout Delay (0.000–60 cycles) 0.500
0.125
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...