SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Basic Relay Operations
Operating the Relay Inputs and Outputs
There are two types of input circuitry: direct-coupled and optoisolated.
lists the main differences between the two types of control inputs. Only the
SEL-421 and SEL-451 are available with interface boards that support direct-
coupled inputs. All SEL-400 series relays support optoisolated inputs.
The default value for Global setting EICIS (Enable Independent Control Input
Settings) is N, which hides all individual control input settings and only presents
some overall settings that will apply to all control inputs. Set EICIS := Y to gain
full access to the individual control input settings.
Setting a Control Input for Circuit Breaker Auxiliary Contacts (52A) in
the Terminal
This is a step-by-step procedure to configure a control input that reflects the state
of the circuit breaker auxiliary (52A) NO (normally open) contact. A common
relay input is from circuit breaker auxiliary contacts; the relay monitors the 52A
contacts to detect the closed/open status of the circuit breaker. Perform the fol-
lowing steps to connect three-pole circuit breaker auxiliary contacts to the relay.
This example was created using an SEL-451. Refer to the product-specific
instruction manual for the correct Relay Word bit names for each product.
This example assumes that you have successfully established communication
with the relay (see
Making an EIA-232 Serial Port Connection on page 3.4
). In
addition, you must be familiar with relay access levels and passwords (see
Changing the Default Passwords in the Terminal on page 3.10
to change the
default access level passwords).
Step 1. Prepare to control the relay at Access Level 2.
a. Using a communications terminal, type
ACC <Enter>
.
b. Type the Access Level 1 password and press
<Enter>
.
You will see the => prompt.
c. Type
2AC <Enter>
.
d. Type the correct password to go to Access Level 2.
You will see the Access Level 2 =>> prompt.
Step 2. Configure the relay to read the circuit breaker auxiliary contact.
a. Type
SET M <Enter>
(see
These settings are the breaker monitor settings.
b. Type
<Enter>
to bypass the Breaker 1 Monitoring enable, and
<Enter>
again to bypass the Breaker 2 Monitoring enable
(NUMBK := 2 in this example).
The relay displays the 52AA1 SEL
OGIC
control equation action
prompt.
Table 3.8
Control Input Characteristics
Direct-Coupled
Optoisolated
Pickup characteristics: Pickup voltage can be selected via Global settings.
Can have different pickup voltages on each input.
Pickup voltage is determined by hardware: one of six volt-
age levels determined at time of factory order. All pickup
voltages are the same on each I/O interface board.
Polarity- sensitive:
Yes (will not respond to reverse polarity signals). A +
polarity mark is printed over the positive terminals.
No (will respond to signals of either polarity). No polarity
mark. AC signal detection is possible.
a
Where found:
INT1, INT5, and INT6 I/O Interface Boards
(available in SEL-421 and SEL-451 relays)
SEL-400 Series Main Board (IN101–IN107)
All other interface boards
a
With appropriate debounce settings (see
Section 2: Installation
of the product-specific instruction manual).
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...