3.21
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Basic Relay Operations
Making Simple Settings Changes
c. Type
2AC <Enter>
.
d. Type the correct password to go to Access Level 2.
You will see the Access Level 2 =>> prompt.
Step 2. Type
SET G NFREQ <Enter>
(this sets the nominal system frequency
using the
NFREQ
setting, which has options of 50 Hz and 60 Hz).
The relay responds with a terminal screen display similar to that
shown in
.
Step 3. Accept the default settings.
a. For a 60 Hz system, press
<Enter>
to accept the NFREQ exist-
ing value of 60 (Hz).
The relay presents the next setting, which is the PHROT (phase
rotation) setting.
b. Type
<Enter>
to accept the ABC phase rotation default.
Step 4. Set the date format:
The relay can report dates in three formats: MDY, YMD, and DMY
(where M = month, D = date, and Y = year).
a. For this procedure, type
YMD <Enter>
.
At each setting in turn, the relay presents the settings prompt,
name, present value, and action prompt.
Note that SEL
OGIC
control equation settings, such as FAULT in
, can appear on multiple lines.
b. If you make a mistake or want to go backward through the
settings, type the ^ character (on most computer keyboards, this
is a shifted numeral 6) and
<Enter>
.
Refer to
for this and other navigational aids.
Step 5. End the settings session.
a. Type
END <Enter>
at the
FAULT
action prompt.
(The Fault SEL
OGIC
control equation remains unchanged.)
The relay next scrolls a readback of all the Global settings,
eventually displaying the following prompt:
Save settings (Y,N) ?
(In
, a vertical ellipsis represents the relay
information during readback.)
b. Examine the settings readback to verify your new settings.
c. Answer
Y <Enter>
to save your new settings.
=>>
SET G NFREQ <Enter>
Global
General Global Settings
Nominal System Frequency (50,60 Hz) NFREQ := 60 ?
<Enter>
System Phase Rotation (ABC,ACB) PHROT := ABC ?
<Enter>
Date Format (MDY,YMD,DMY) DATE_F := MDY ?
YMD
<Enter>
Fault Condition Equation (SELogic Equation)
FAULT := 51S1 OR 51S2 OR 50P1
?
END <Enter>
•
•
•
Save settings (Y,N) ?
Y <Enter>
Saving Settings, Please Wait...........
Settings Saved
=>>
Figure 3.16
Example Global Settings
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...