6.129
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
Out-of-Step Logic Application Examples
For those applications that allow the relay to operate for any internal and external
faults on a system during a power swing, set the 67Q1T element similar to the
67QUBF element:
50Q1P :=
same value as of 50QUBP
.
Level 1 Pickup (OFF, 0.25–100 Amps
sec.)
67Q1D :=
same value as of UBD
.
Level 1 Time Delay (0.000–16000 cycles)
67Q1TC :=
1
.
Level 1 Torque Control (SEL
OGIC
Equation)
For those applications that require the relay only trip for internal faults during a
power swing, disable the 67Q1T element by setting 50Q1P to OFF or E50Q = N.
This way, the Zone 1 distance elements are always blocked by the OSB logic.
The relay relies on Zone 2 overreaching elements together with the POTT
scheme to make high-speed trips for internal faults.
Example Completed
This completes the application example that describes setting the SEL-421 for
out-of-step blocking. Analyze your particular power system to determine the
appropriate settings for your application.
Relay Settings
lists the settings that the relay automatically calculates and hides when
you set EADVS to N and EOOST to N.
list the protective relay settings available in this example.
Table 6.33
Automatically Calculated/Hidden Settings
Setting
Prompt
Default Setting
X1B7
Zone 7 Reactance—Bottom (–0.05 to –140
secondary)
X1B7 = –X1T7
X1B6
Zone 6 Reactance—Bottom (–0.05 to –140
secondary)
X1B6 = –X1T6
R1L7
Zone 7 Resistance—Left (–0.05 to –140
secondary)
R1L7 = –R1R7
R1L6
Zone 6 Resistance—Left (–0.05 to –140
secondary)
R1L6 = –R1R6
OSTD
Out-of-Step Trip Delay (0.500–8000 cycles)
0.500
50ABCP
Positive-Sequence Current Supervision (1.00–100 A secondary) 50ABCP = 0.2 • I
NOM
50QUBP
Negative-Sequence Current Supervision
(OFF, 0.50–100 A secondary)
OFF
UBD
Negative-Sequence Current Unblock Delay
(0.500–120 cycles)
0.500
UBOSBF Out-of-Step Angle Unblock Rate (1–10)
4
Table 6.34
Relay Configuration (Group)
Setting
Prompt
Entry
EOOS
Out-of-Step (Y, Y1, N)
Y
EADVS
Advanced Settings (Y, N)
N
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...