17.9
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
IEC 61850 Communication
IEC 61850 Operation
File Services
The Ethernet file system allows reading or writing data as files. The file system
supports FTP and MMS file transfer. The file system provides:
➤
A means for the device to transfer data as files.
➤
A hierarchal file structure for the device data.
The relay supports MMS file transfer with or without authentication. Note that
the MMS File Transfer service will still be supported even if the relay contains an
invalid CID file. The service is intended to support:
➤
Settings file download and upload
➤
CID file download and upload
➤
Event report retrieval
MMS File Services are enabled or disabled via Port 5 settings, EMMSFS. Per-
missions for the 2AC level apply to MMS File Services requests. All files and
directories that are available at the 2AC access level via any supported file trans-
fer mechanism (FTP, file read/write, etc.) are also available for transfer via MMS
File Services.
SCL Files
Substation Configuration Language (SCL) is an XML-based configuration lan-
guage used to support the exchange of database configuration data between dif-
ferent tools, which may come from different manufacturers. There are four types
of SCL files:
➤
IED Capability Description file (.ICD)
➤
System Specification Description (.SSD) file
➤
Substation Configuration Description file (.SCD)
➤
Configured IED Description file (.CID)
The ICD file describes the capabilities of an IED, including information on LN
and GOOSE support. The SSD file describes the single-line diagram of the sub-
station and the required LNs. The SCD file contains information on all IEDs,
communications configuration data, and a substation description. The CID file,
of which there may be several, describes a single instantiated IED within the
project, and includes address information.
Reports
The relay supports buffered and unbuffered report control blocks in the report
model as defined in IEC 61850-8-1:2011. The predefined reports shown in
are available by default via IEC 61850.
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...