![Schweitzer Engineering Laboratories SEL-421-4 Скачать руководство пользователя страница 449](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726449.webp)
6.113
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
TRSOTF
The TRSOTF SEL
OGIC
control equation defines which protection elements cause
the relay to trip when the SOTF scheme is active. Assertion of these protection
elements during the SOTFD time causes the relay to trip instantaneously (see
). Set instantaneous Zone 2 distance protection
(Z2G) and Level 1 phase instantaneous overcurrent element (50P1) in the
TRSOTF SEL
OGIC
control equation.
TRSOTF := Z2P OR Z2G OR 50P1.
Switch-Onto-Fault Trip (SEL
OGIC
Equation)
Trip Unlatch Options
Unlatch the control output you programmed for tripping (OUT101) after the cir-
cuit breaker auxiliary a contacts break the dc current. The SEL-421 provides two
methods for unlatching control outputs following a protection trip:
➤
ULTR—all three poles
➤
TULO—phase selective
ULTR
Use ULTR, the Unlatch Trip SEL
OGIC
control equation, to unlatch all three
poles. Use the default setting to assert ULTR when you push the front-panel tar-
get reset button.
ULTR :=
TRGTR
.
Unlatch Trip (SEL
OGIC
Equation)
TULO
Use TULO (Trip Unlatch Option) to select the conditions that cause the SEL-421
to unlatch the control outputs that you programmed for tripping.
shows the four trip unlatch options for setting TULO.
Select Option 3 because a 52A contact is available; the relay uses both open-
phase detection and status information from the circuit breaker to make the most
secure decision. For information on the pole-open logic, see
TULO :=
3
.
Trip Unlatch Option (1, 2, 3, 4)
Table 6.30
Setting TULO Unlatch Trip Options
Option
Description
1
Unlatch the trip when the relay detects that one or more poles of the line termi-
nal are open, and Relay Word bit 3PT has deasserted.
2
Unlatch the trip when the relay detects that the corresponding 52A contact(s)
from both circuit breakers (52AA1 and 52AA2) are deasserted.
3
Unlatch the trip when the relay detects that the conditions for Options 1 and 2
are satisfied.
4
Do not run this logic.
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...