6.50
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
500 kV Parallel Transmission Lines With Mutual Coupling Example
Mho Ground-Distance Element Reach (Group)
Z1MG
Zone 1 (OFF, 0.05–64
secondary)
3.18
Z2MG
Zone 2 (OFF, 0.05–64
secondary)
4.78
Z3MG
Zone 3 (OFF, 0.05–64
secondary)
4.78
Quadrilateral Ground-Distance Element Reach (Group)
XG1
Zone 1 Reactance (OFF, 0.05–64
secondary)
3.18
RG1
Zone 1 Resistance (0.05–50
secondary)
7.96
XG2
Zone 2 Reactance (OFF, 0.05–64
secondary)
4.78
RG2
Zone 2 Resistance (0.05–50
secondary)
12.00
XG3
Zone 3 Reactance (OFF, 0.05–64
secondary)
4.78
RG3
Zone 3 Resistance (0.05–50
secondary)
15.00
XGPOL
Quadrilateral Ground Polarizing Quantity (I2, IG)
I2
TANGG
Nonhomogeneous Correction Angle
(–40.0 to +40.0 degrees)
0.0
Zero-Sequence Current Compensation Factor (Group)
k0M1
Zone 1 ZSC Factor Magnitude (AUTO, 0.000–10)
0.880
k0A1
Zone 1 ZSC Factor Angle
(–180.0 to +180.0 degrees)
–7.6
k0M
Forward Zones ZSC Factor Magnitude (0.000–10)
1.540
k0A
Forward Zones ZSC Factor Angle
(–180.0 to +180.0 degrees)
–9.0
k0MR
Reverse Zones ZSC Factor Magnitude (0.000–10)
1.540
k0AR
Reverse Zones ZSC Factor Angle
(–180.0 to +180.0 degrees)
–9.0
Ground-Distance Element Time Delay (Group)
Z1GD
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z2GD
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z3GD
Zone 3 Time Delay (OFF, 0.000–16000 cycles)
OFF
Distance Element Common Time Delay (Group)
Z1D
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
0.000
Z2D
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
20.000
Z3D
Zone 3 Time Delay (OFF, 0.000–16000 cycles)
0.000
SOTF Scheme Settings
ESPSTF
Single-Pole Switch-Onto-Fault (Y, N)
Y
EVRST
Switch-Onto-Fault Voltage Reset (Y, N)
Y
VRSTPU
Switch-Onto-Fault Reset Voltage (0.60–1.00 pu)
0.60–1.00 pu
52AEND
52A Pole Open Time Delay
(OFF, 0.000–16000 cycles)
10.000
CLOEND
CLSMON or Single Pole Open Delay
(OFF, 0.000–16000 cycles)
OFF
SOTFD
Switch-Onto-Fault Enable Duration
(0.500–16000 cycles)
10.000
CLSMON
Close Signal Monitor (SEL
OGIC
Equation)
NA
Table 6.13
Settings for 500 kV Parallel TX Example (Sheet 4 of 7)
Setting
Prompt
Entry
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...