6.118
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
Selectable Operating Quantity Inverse-Time Overcurrent Element 1 (Group)
51S1O
51S1 Op. Qty (IA
n
, IB
n
, IC
n
, IMAX
n
, I1L, 3I2L,
3I0
n
)
a
3I2L
51S1P
51S1 O/C Pickup (0.25–16 A secondary)
1.00
51S1C
51S1 Inverse Time O/C Curve (U1–U5)
U3
51S1TD
51S1 Inverse Time O/C Time Dial (0.50–15)
3.72
51S1RS
51S1 Inverse Time O/C EM Reset (Y, N)
Y
51S1TC
51S1 Torque Control (SEL
OGIC
Equation)
32GF
Zone/Level Direction (Group)
DIR3
Zone/Level 3 Directional Control (F, R)
R
Directional Control (Group)
ORDER
Ground Dir. Element Priority (combine Q, V, I)
Q
Pole-Open Detection (Group)
EPO
Pole Open Detection (52, V)
52
SPOD
Single Pole Open Dropout Delay (0.000–60 cycles) 0.500
3POD
Three Pole Open Dropout Delay (0.000–60 cycles) 0.500
POTT Trip Scheme (Group)
Z3RBD
Zone 3 Reverse Block Time Delay (0.000–16000
cycles)
5.000
EBLKD
Echo Block Time Delay (OFF, 0.000–16000
cycles)
10.000
ETDPU
Echo Time Delay Pickup (OFF, 0.000–16000
cycles)
2.000
EDURD
Echo Duration Time Delay (0.000–16000 cycles)
4.000
EWFC
Weak Infeed Trip (Y, N, SP)
N
PT1
General Permissive Trip Received
(SEL
OGIC
Equation)
IN103
Trip Logic (Group)
TR
Trip (SEL
OGIC
Equation)
Z1T OR Z2T OR 51S1T
TRCOMM
Communications-Assisted Trip
(SEL
OGIC
Equation)
Z2P OR 67Q2
TRCOMMD
Dir. Element Comms.-Assisted Trip
(SEL
OGIC
Equation)
NA
TRSOTF
Switch-Onto-Fault Trip (SEL
OGIC
Equation)
Z2P OR Z2G OR 50P1
DTA
Direct Transfer Trip A-Phase (SEL
OGIC
Equation)
NA
DTB
Direct Transfer Trip B-Phase (SEL
OGIC
Equation)
NA
DTC
Direct Transfer Trip C-Phase (SEL
OGIC
Equation)
NA
BK1MTR
Manual Trip–Breaker 1 (SEL
OGIC
Equation)
OC1 OR PB8_PUL
ULTR
Unlatch Trip (SEL
OGIC
Equation)
TRGTR
ULMTR1
Unlatch Manual Trip–Breaker 1
(SEL
OGIC
Equation)
NOT (52AA1 AND
52AB1 AND 52AC1)
TOPD
Trip During Open Pole Time Delay
(2.000–8000 cycles)
2.000
TULO
Trip Unlatch Option (1, 2, 3, 4)
3
Table 6.31
Settings for 230 kV Parallel Cables Example (Sheet 4 of 5)
Setting
Prompt
Entry
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...