5.50
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Functions
Out-of-Step Logic (Conventional)
Out-of-Step Logic (Conventional)
The SEL-421 offers both conventional and settingless (zero-setting) out-of-step
(OOS) functions. To use the conventional OOS function, set EOOS = Y. To use
the zero-setting OOS function, set EOOS = Y1.
The out-of-step (OOS) logic determines whether a power swing is stable. This
relay logic can be set to either block distance protection or allow tripping when
the measured positive-sequence impedance (Z
1
) remains between inner Zone 6
and outer Zone 7 longer than either the OOS blocking delay (setting OSBD) or
the OOS tripping delay (setting OSTD), respectively (refer to
).
NOTE:
E50Q must be set to 1 or
greater for enabling 67Q1T override of
OOS blocking for Zone 1 (see
, and
).
The OOS logic detects all power swings that enter the OOS characteristics, even
if a single-pole open condition exists (Relay Word bit SPO equals logical 1). If
either negative-sequence directional element 67QUBF or 67QUBR (67Q1T for
Zone 1) picks up during a power swing and a single-pole open condition does not
exist (Relay Word bit SPO equals logical 0), the logic overrides OOS blocking
Figure 5.31
Load-Encroachment Characteristics
ZLIN
(Load In
Region)
(180˚)
(90˚)
X1
PLAR
PLAF
NLAR
NLAF
ZLF
ZLR
(270˚) (—90˚)
ZLOUT
(Load Out
Region)
(0˚)
R1
Table 5.44
Load-Encroachment Logic Relay Settings
Setting
Prompt
Range
Default
(5 A)
ELOAD
Load Encroachment
Y, N
Y
ZLF
Forward Load Impedance (
)
(0.25–320)/I
NOM
9.22
ZLR
Reverse Load Impedance (
)
(0.25–320)/I
NOM
9.22
PLAF
Forward Load Positive angle (°)
–90.0 to +90
30.0
NLAF
Forward Load Negative angle (°)
–90.0 to +90
–30.0
PLAR
Reverse Load Positive angle (°)
90.0–270
150.0
NLAR
Reverse Load Negative angle (°)
90.0–270
210.0
Table 5.45
Load-Encroachment Logic Relay Word Bits
Name
Description
ZLOAD
ZLIN OR ZLOUT
ZLIN
Import load impedance detected
ZLOUT
Export load impedance detected
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...