18.24
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Synchrophasors
C37.118 Synchrophasor Protocol
Communications Bandwidth
A phasor measurement unit (PMU) that is configured to transmit a single syn-
chrophasor (positive-sequence voltage, for example) at a message rate of once
per second places little burden on the communications channel. As more syn-
chrophasors, analog values, or digital status words are added, or if the message
rate is increased, some communications channel restrictions come into play.
If the SPEED setting on any serial port set with PROTO := PMU is insufficient
for the PMU Global settings, the relay or QuickSet will display an error message
and fail to save settings until the error is corrected.
The C37.118 synchrophasor message format always includes 16 bytes for the
message header and terminal ID, time information, and status bits. The selection
of synchrophasor data, numeric format, programmable analog, and programma-
ble digital data will add to the byte requirements.
can be used to cal-
culate the number of bytes in a synchrophasor message.
lists the bps settings available on any relay serial port (setting
SPEED), and the maximum message size that can fit within the port bandwidth.
Blank entries indicate bandwidths of less than 20 bytes.
Table 18.13
Size of a C37.118 Synchrophasor Message
Item
Possible
number of
quantities
Bytes per
quantity
Minimum
number of
bytes
Maximum
number of
bytes
Fixed
18
18
Synchrophasors
a
a
Some SEL relays have a smaller number of possible synchrophasors.
0, 1, 2…32
4 (PHNR := I)
8 (PHNR := F)
0
256
Frequency
2 (fixed)
2 (FNR := I)
4 (FNR := F)
4
8
Analog Values
0 – 16
4
0
64
Digital Status Words
0 – 4
2
0
8
Total (Minimum and Maximum)
22
354
Table 18.14
Serial Port Bandwidth for Synchrophasors (in Bytes) (Sheet 1 of 2)
Global Setting
MRATE
Port Setting SPEED
300
600
1200
2400
4800
9600
19200
38400
57600
1
21
42
85
170
340
680
1360
2720
4080
2
21
42
85
170
340
680
1360
2040
4 (60 Hz only)
21
42
85
170
340
680
1020
5
34
68
136
272
544
816
10
34
68
136
272
408
12 (60 Hz only)
28
56
113
226
340
15 (60 Hz only)
21
45
90
181
272
20 (60 Hz only)
34
68
136
204
25 (50 Hz only)
27
54
108
163
Содержание SEL-421-4
Страница 6: ...This page intentionally left blank ...
Страница 14: ...This page intentionally left blank ...
Страница 30: ...This page intentionally left blank ...
Страница 104: ...This page intentionally left blank ...
Страница 128: ...This page intentionally left blank ...
Страница 536: ...This page intentionally left blank ...
Страница 584: ...This page intentionally left blank ...
Страница 616: ...This page intentionally left blank ...
Страница 696: ...This page intentionally left blank ...
Страница 750: ...This page intentionally left blank ...
Страница 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Страница 776: ...This page intentionally left blank ...
Страница 932: ...This page intentionally left blank ...
Страница 976: ...This page intentionally left blank ...
Страница 1024: ...This page intentionally left blank ...
Страница 1038: ...This page intentionally left blank ...
Страница 1064: ...This page intentionally left blank ...
Страница 1128: ...This page intentionally left blank ...
Страница 1206: ...This page intentionally left blank ...
Страница 1316: ...This page intentionally left blank ...
Страница 1350: ...This page intentionally left blank ...
Страница 1464: ...This page intentionally left blank ...
Страница 1468: ...This page intentionally left blank ...
Страница 1492: ...This page intentionally left blank ...
Страница 1518: ...This page intentionally left blank ...