31
A
R
A
4. Checking/setting the gas/air ratio at full load
The Avanta Plus boilers are suitable for both natural gas and
propane firing. For the Avanta Plus 39c an optional propane-
set is needed.
The boilers are supplied as standard set for natural gas
(H), therefore the following procedure must be carried out
BEFORE the boilers are fired and commissioned for the first
time on propane:
-
adjust the fan speed (
for procedure; see Par. 2.9.8, for
values; see table 06 and
table 08) and;
-
adjust the gas/air ratio (
for values; see table 06 and table 08
).
LT.AL.W7H.000.042
Setting values O
2
/CO
2
for natural gas H / L
Boiler type
Fan speed (rpm)
O
2
CO
2
Full load
h3
*)
% %
24s
approx. 4300
5.2
± 0.1
8.8
± 0.1
28c
approx. 5500
5.2
± 0.1
8.8
± 0.1
35c
approx. 6300
5.2
± 0.1
8.8
± 0.1
39c
approx. 6700
5.2
± 0.1
8.8
± 0.1
table 05 Setting values full load CO
2
and O
2
(front panel not
fi
tted)
Setting values O
2
/CO
2
for LPG (propane)
Boiler type
Fan speed (rpm)
O
2
CO
2
Full load
h3
*)
% %
24s
approx. 4100
5.1
± 0.3
10.5
± 0.3
28c
approx. 5200
5.1
± 0.1
10.5
± 0.3
35c
approx. 5800
5.1
± 0.3
10.5
± 0.3
39c
approx. 6500
5.1
± 0.3
10.5
± 0.3
table 06 Setting values full load CO
2
and O
2
(front panel not
fi
tted)
*) On forced full load, the 2
nd
digit indicates the operating code
•
Unscrew the flue gas sampling cap and connect the flue gas
analyser.
•
Set boiler to full load.
•
Press the
[enter]-
key, keep it pressed and also press the
[+]-
key until
h3
appears in the display; full load has been
set.
•
Once the unit has reached the full-load fan speed, measure
the O
2
/CO
2
-percentage and compare this to the values in
table 05.
•
If the values are not in accordance with the table then correct
the gas /air ratio controls using the adjusting screw A on the
gas block.
•
If the value is too low turn the screw A anti clockwise; this
increases the gas rate – if the value is too high turn the screw
clockwise which decreases the gas rate.
•
Check the flame through the sight glass which should be sta-
ble with a regular blue distribution.
Содержание Avanta Plus 24s
Страница 94: ...30...
Страница 95: ...31...
Страница 97: ...2 AVANTA PLUS 28 Combi Gas Council No 47 673 02 39 Combi Gas Council No 47 673 04...
Страница 100: ...5...
Страница 104: ...9...
Страница 107: ...12 AVANTA PLUS 24 System Gas Council No 41 288 05...
Страница 110: ...15...
Страница 118: ...User guide Remeha Avanta Plus Remeha Avanta Plus 28c Remeha Avanta Plus 39c Remeha Avanta Plus 24s...
Страница 146: ...1 Issue No 1 Date 8 December 2005 Operating instructions for the built in Two Channel Digital electronic time clock...
Страница 149: ...4 6 Description of setting buttons and display M T W Th F S Su DAY HR MIN Set 5 Position of Timer in boiler when fitted...