POWER ELECTRONICS
SDRIVE 700
DESCRIPTION OF PROGRAMMING PARAMETERS
85
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
5 SETPT1=0.0Bar
LOCAL SETPOINT 1
G25.1.5
/ Local
setpoint 1 for PID
YES
6 SETPT2=0.0Bar
LOCAL SETPOINT 2
G25.1.6
/ Local
setpoint 2 for PID
YES
7 SETPT3=0.0Bar
LOCAL SETPOINT 3
G25.1.7
/ Local
setpoint 3 for PID
YES
8 SETPT4=0.0Bar
LOCAL SETPOINT 4
G25.1.8
/ Local
setpoint 4 for PID
YES
9 SETPT5=0.0Bar
LOCAL SETPOINT 5
G25.1.9
/ Local
setpoint 5 for PID
YES
10 SETPT6=0.0Bar
LOCAL SETPOINT 6
G25.1.10
/ Local
setpoint 6 for PID
YES
11 SETPT7=0.0Bar
LOCAL SETPOINT 7
G25.1.11
/ Local
setpoint 7 for PID
YES
12 SETPT8=0.0Bar
LOCAL SETPOINT 8
G25.1.12
/ Local
setpoint 8 for PID
0 – 3276
Engineering
Units
0.0Bar
In case of operation with only one local setpoint for PID, the value
will be the set value in G25.1.5.
The applied speed in each case will depend on the activation status
of the digital inputs configured as options ’63 SETPONT PIN1’, ’64
SETPONT PIN2’ and ’65 SETPONT PIN3’.
The assigned speed will be done according to the attached table:
DIGITAL INPUTS
DI(z)=65
DI(y)=64
DI(x)=63
PID SETPOINTS
0 0 0
G25.1.5
‘SETPT1’
0 0 X
G25.1.6
‘SETPT2’
0 X 0
G25.1.7
‘SETPT3’
0 X X
G25.1.8
‘SETPT4’
X 0 0
G25.1.9
‘SETPT5’
X 0 X
G25.1.10
‘SETPT6’
X X 0
G25.1.11
‘SETPT7’
X X X
G25.1.12
‘SETPT8’
Note
: It is possible to operate with the following units %, l/s, m/s,
l/min, m³/min, l/h, m³/h, m/s, m/min, m/h, Bar, Kpa, Psi, m, ºC, ºF,
ºK. It depends on the units of the sensor used.
YES
13 T AutOFF=OFF
AUTO-OFF DELAY
G25.1.13
/ Time
for automatic
stop
OFF,
0.1 – 99.9h
OFF
User can set a run time that once elapsed the drive will stop
automatically. When set this time value starts to elapse immediately
and the drive will stop once this time has expired. At that moment
the parameter value becomes OFF and the status of the program
will change to ‘COMPLETED’. If you want to the drive to stop
automatically again, you must reset the stop time.
There are two visualization parameters related with this parameter:
‘SV5.22 T AutOFF= OFF’ it is directly the G25.1.13, translated to
the visualization group SV5.
‘SV5.23 TIME OFF= OFF’ that shows the remaining time in minutes
for the automatic stop of the system.
YES