SDRIVE 700
POWER ELECTRONICS
62
DESCRIPTION OF PROGRAMMING PARAMETERS
10.8.2.
Subgroup 8.2 – S8.2: Analogue Outputs
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
1 ANLG OUT1=01
G8.2.1
/ Mode
selection for
Analogue Output
1
00 – 27
01
Analogue output is programmable according to the following table:
OPT
DESCR.
FUNCTION
UNITS
00
NONE
It is not used.
-
01
SPEED
MOTOR
Signal proportional to the
motor speed.
% Motor
speed
02
CURRENT
MOTOR
Signal proportional to the
motor current.
% Motor
rated current
03
VOLTAGE
MOTOR
Signal proportional to the
motor voltage.
% Motor
rated voltage
04
POWER
MOTOR
Signal proportional to the
motor power.
% Motor
power
05
TORQUE
MOTOR
Signal proportional to the
motor torque.
% Motor
torque
06
PF MOTOR
Signal proportional to the
motor power factor.
% Motor
rated Cosine
Phi
07
TEMP
MOTOR
Signal proportional to the
motor temperature.
% Motor
temperature
08
FREQUENC
Y MTR
Signal proportional to the
input frequency.
% Input
frequency
(50Hz=100%)
09
INPUT
VOLTAGE
Signal proportional to the
input voltage.
% Equipment
rated voltage
10
DC BUS
Signal proportional to the
DC Bus voltage.
% Motor
voltage x
1.414
11
DRIVE
TEMP
Signal proportional to the
drive temperature.
% Drive
temperature
12
SPEED REF
Signal proportional to the
speed reference.
% Motor
speed
13
Reserved
Reserved for future use.
14
PID
REFERENC
E
Signal proportional to the
reference in PID mode.
%
15
PID
FEEDBACK
Signal proportional to the
feedback in PID mode.
%
16
PID ERROR
Signal proportional to the
error (difference
between reference and
feedback) in PID mode.
%
17
ANLG INPUT
1
Analogue input 1 signal
is transferred to
analogue output.
%
18
ANLG INPUT
2
Analogue input 2 signal
is transferred to
analogue output.
%
19
ANLG INPUT
1+2
Signal proportional to the
addition of the two
inputs. This allows
course and fine setting
of the signal.
%
20
CURRENT
FLOW
Analogue signal
proportional to the read
flow through analogue
input or pulse input.
%
Note:
See following page.
NO