DESCRIPTION OF PROGRAMMING PARAMETERS
89
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
12 I SLEEP=xxxA
CURR SLEEP LEVEL
G25.4.12
/
Output current
level to sleep the
drive
OFF=0 to
1229A
xxxA
Output current will be monitored and when it is below the level set
here, sleep time will start elapsing. Once elapsed this time, the
equipment will go in sleep mode. So it allows setting the level of the
output current, below which, a situation of ‘no demand’ will be
detected. This situation will send to sleep the drive. When this
parameter is set to OFF, it will be disabled.
Note
: The drive can go to sleep in all of the conditions
simultaneously. Any fulfilled condition will begin the sleep delay time
or will keep it active in case of the condition that began it
disappears.
YES
13 FP erOFF=+0.0%
FPUMP STOP ERROR
G25.4.13
/
Maximum PID
error to stop the
fixed pumps
OFF=0 to
+100%
+0.0%
It sets the PID error below which, fixed pumps will be stopped. Any
error value more negative than the value set here will stop a fixed
pump. This condition is optional.
This parameter allows user the possibility of considering the PID
error (%) at the moment of stopping the fixed pumps. Additionally,
the drive speed and a stop delay time for each fixed pump
(whenever you want) will be considered.
Note
: PID error conditions, delay time and speed are optional and
can be configured to be considered or not, such as it has been
explained for the starting conditions of fixed pumps.
YES
14 FP T1 OF=10s
FPUMP1 STP DELAY
G25.4.14
/
Delay time to
stop fixed pump
1 (Relay 1)
0 – 6000s
10s
To set the delay time for the fixed pump assigned to the relay 1.
Note:
It time is too short, overpressure could occur in the system. If
time is too long under-pressure could occur.
YES
15 FP T2 OF=10s
FPUMP2 STP DELAY
G25.4.15
/
Delay time to
stop fixed pump
2 (Relay 2)
0 – 6000s
10s
To set the delay time for the fixed pump assigned to the relay 2.
Note:
It time is too short, overpressure could occur in the system. If
time is too long under-pressure could occur.
YES
16 FP T3 OF=10s
FPUMP3 STP DELAY
G25.4.16
/
Delay time to
stop fixed pump
3 (Relay 3)
0 – 6000s
10s
To set the delay time for the fixed pump assigned to the relay 3.
Note:
It time is too short, overpressure could occur in the system. If
time is too long under-pressure could occur.
YES
17 FP T4 OF=10s
FPUMP4 STP DELAY
G25.4.17
/
Delay time to
stop fixed pump
4 (AO1)
0 – 6000s
10s
To set the delay time for the fixed pump assigned to the Analogue
Output 1.
Note:
It time is too short, overpressure could occur in the system. If
time is too long under-pressure could occur.
YES
18 FP T5 OF=10s
FPUMP5 STP DELAY
G25.4.18
/
Delay time to
stop fixed pump
5 (AO2)
0 – 6000s
10s
To set the delay time for the fixed pump assigned to the Analogue
Output 2.
Note:
It time is too short, overpressure could occur in the system. If
time is too long under-pressure could occur.
YES
19 70.0%
FPUMP STP SPEED1
G25.4.19
/ Stop
speed 1 for one
fixed pump
+0.0% to
+250%
+70.0%
It sets the speed below which the drive must remain for stopping a
fixed pump whenever the operating setpoint is the local setpoint 1
set in G25.1.5.
If you want the speed condition is not considered for stopping the
fixed pumps, you must set a value that will be always above the
drive speed, so that, this condition is always fulfilled and therefore, it
would stop being a condition. This is applicable to all of the selected
setpoints.
YES
20 70.0%
FPUMP STP SPEED2
G25.4.20
/ Stop
speed 2 for one
fixed pump
+0.0% to
+250%
+70.0%
It sets the speed below which the drive must remain for stopping a
fixed pump whenever the operating setpoint is the local setpoint 2
set in G25.1.6.
YES
21 70.0%
FPUMP STP SPEED3
G25.4.21
/ Stop
speed 3 for one
fixed pump
+0.0% to
+250%
+70.0%
It sets the speed below which the drive must remain for stopping a
fixed pump whenever the operating setpoint is the local setpoint 3
set in G25.1.7.
YES
22 70.0%
FPUMP STP SPEED4
G25.4.22
/ Stop
speed 4 for one
fixed pump
+0.0% to
+250%
+70.0%
It sets the speed below which the drive must remain for stopping a
fixed pump whenever the operating setpoint is the local setpoint 4
set in G25.1.8.
YES
23 70.0%
FPUMP STP SPEED5
G25.4.23
/ Stop
speed 5 for one
fixed pump
+0.0% to
+250%
+70.0%
It sets the speed below which the drive must remain for stopping a
fixed pump whenever the operating setpoint is the local setpoint 5
set in G25.1.9.
YES