SDRIVE 700
POWER ELECTRONICS
108
COMMONLY USED CONFIGURATIONS
12.4.
Start / Stop Commands by Terminals and Seven Speed
References Selectable by Digital Inputs
12.4.1.
Parameters Configuration
Parameter
Name / Description
Value
G1: Options Menu.
4 LANG=ENGLISH
G1.4
/ Language selection
ENGLISH
7 PROG = STANDAR
G1.7
/ Program activation
STANDAR
G2: Motor Nameplate.
1 MTR CURR=00.00A
G2.1
/ Motor rated current
__A (Set according to motor nameplate).
2 MTR VOLT=400V
G2.2
/ Motor rated voltage
__V (Set according to motor nameplate).
3 MTR PWR=00.0kW
G2.3
/ Motor rated power
__kW (Set according to motor nameplate).
4 MTR RPM=1485
G2.4
/ Motor rpm
__rpm (Set according to motor nameplate).
5 MTR PFA=0.85
G2.5
/ Cosine Phi
__ (Set according to motor nameplate).
6 MTR FRQ=50Hz
G2.6
/ Motor frequency
__Hz (Set according to motor nameplate).
7 MTR COOL=40%
G2.7
/ Motor cooling at zero speed
Use the following values as a reference:
Submersible pumps
Î
20%
Self-cool motor
Î
40%
Force-cooled motor
Î
100%
G3: References.
1 REF1 SPD=MREF
G3.1
/ Speed reference source 1
MREF
Î
Multiple speed references activated by digital inputs.
G4: Inputs – S4.1: Digital Inputs.
1 CNTROL MODE1=2
G4.1.1
/ Main Control Mode
2
Î
REMOTE (Drive control is done through control terminals).
4 DIGIT I MODE=3
G4.1.4
/ Digital Inputs configuration
selection
3
Î
MREF 3 WIRES (Automatically programs digital inputs 4, 5
and 6 as multiple speed references for up to 7 different values. The
others digital inputs remain user configurable).
5 DIGITL IN 1=05
G4.1.5
/ Multi-function Digital Input 1
configuration
05
Î
Start/Stop (Allows the start/stop command to be given by a
switch).
G14: Multi-references.
1 MREF 1=+10.0%
G14.1
/ Multi-reference 1
+10.0% (Allows setting the setpoint 1 value for the drive. It should
be set according to the application requirements).
2 MREF 2=+20.0%
G14.2
/ Multi-reference 2
+20.0% (Allows setting the setpoint 2 value for the drive. It should
be set according to the application requirements).
3 MREF 3=+30.0%
G14.3
/ Multi-reference 3
+30.0% (Allows setting the setpoint 3 value for the drive. It should
be set according to the application requirements).
4 MREF 4=+40.0%
G14.4
/ Multi-reference 4
+40.0% (Allows setting the setpoint 4 value for the drive. It should
be set according to the application requirements).
5 MREF 5=+50.0%
G14.5
/ Multi-reference 5
+50.0% (Allows setting the setpoint 5 value for the drive. It should
be set according to the application requirements).
6 MREF 6=+60.0%
G14.6
/ Multi-reference 6
+60.0% (Allows setting the setpoint 6 value for the drive. It should
be set according to the application requirements).
7 MREF 7=+70.0%
G14.7
/ Multi-reference 7
+70.0% (Allows setting the setpoint 7 value for the drive. It should
be set according to the application requirements).
12.4.2.
Connections Drawing
Terminals 1 and 2: start / stop command (NO status).
Terminals 1 and 5: multi-reference A (NO status).
Terminals 1 and 6: multi-reference M (NO status).
Terminals 1 and 7: multi-reference B (NO status).