SDRIVE 700
POWER ELECTRONICS
126
CONFIGURATION REGISTER
PARAMETERS
FACTORY SETTINGS
SETTING 1
SETTING 2
G25: Pump Control – S25.5: Speed Bypass
1 BY SPon=+70.0%
BYPASS ON SPEED
+70.0% ___________________
___________________
2 BY T ON=10s
BYPASS ON DELAY
10s ___________________
___________________
3 BY SPof=+90.0%
BYPASS OFF SPEED
+90% ___________________
___________________
4 BY T OFF=5s
BYPASS OFF DELAY
5s ___________________
___________________
G25: Pump Control – S25.6: Protection
1 PAUSE/DEL=20s
DELAY AFTER PAUS
20s ___________________
___________________
2 CAVITATION=N
N ___________________
___________________
3 CAV MODE=FAULT
FAULT ___________________
___________________
4 CAV CURR=___A
CAVITATION CURRE
___A ___________________
___________________
5 CAV SPED=+100%
CAVITATION SPEED
+100% ___________________
___________________
6 CAV DELAY=10s
CAVIT FLT DELAY
10s ___________________
___________________
7 ENABLE LO PRE=N
N ___________________
___________________
9 LO PRE=5.0Bar
LO PRESSURE LEVL
5.0Bar ___________________
___________________
10 Lop DLY=10.0s
LO PRESS FLT DLY
10.0s ___________________
___________________
11 Lop Msp=+0.0%
LO PRESS MIN SPED
+0.0% ___________________
___________________
12 HP MODE=PAUSE
PAUSE ___________________
___________________
13 HP LEV=100Bar
HIFH PRESS LEVEL
100Bar ___________________
___________________
14 HIpr DLY=0.0s
HI PRESS FLT DLY
0.0s ___________________
___________________
15 FLO SWm=PAUSE
PAUSE ___________________
___________________
16 NO FLO/FILL=N
N ___________________
___________________
17 NO FLsp=+0.0%
NO FLOW MIN SPED
+0.0% ___________________
___________________
18 NO FLbyp=0.0s
NO FLO BYPAS DLY
0.0s ___________________
___________________
19 NO FLdly=0.0s
NO FLOW FLT DLY
0.0s ___________________
___________________
20 CYCLE TI=0m
CYCLE RESET DELY
0m ___________________
___________________
21 CYCLE CNT=5
MAX CYCLES ALLOW
5 ___________________
___________________
G25: Pump Control – S25.7: Pipe Filling / Setpoint Ramp
1 PRESSU SOU=PID
PID ___________________
___________________
2 FILL SP=+70.0%
PIPE FILLING SPD
+70% ___________________
___________________
3 FILL P=2.0Bar
PFILL END PRESSU
2.0% ___________________
___________________
4 FILL TIM=15m
PFILL END DELAY
15m ___________________
___________________
5 SPT RAMP=1.0Bar / s
1.0Bar / s
___________________
___________________