POWER ELECTRONICS
SDRIVE 700
DESCRIPTION OF PROGRAMMING PARAMETERS
73
10.13.
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
1 F0 NO FAULT
LAST FAULT=FXX
G13.1
/ Screen
for GENERAL
FAULT
- -
Displays last fault information. Drive shows this screen in the case
of a trip.
Pressing
∗
key approx two seconds provides access to the
extended information that shows the order of fault: LAST
FAULT=Fxx (when fault is reset).
The equipment is reset by pressing the STOP-RESET key from
display or by using an external reset (if connected). Several faults
can be reset automatically using Auto Reset (See group G12).
-
2 F0 NO FAULT
FIFTH FAULT=FXX
G13.2
/ Register
1 of fault history
- -
3 F0 NO FAULT
FOURTH FAULT=FXX
G13.3
/ Register
2 of fault history
- -
4 F0 NO FAULT
THIRD FAULT=FXX
G13.4
/ Register
3 of fault history
- -
5 F0 NO FAULT
SECOND FAULT=FXX
G13.5
/ Register
4 of fault history
- -
6 F0 NO FAULT
FIRST FAULT=FXX
G13.6
/ Register
5 of fault history
- -
Register of last five faults.
It shows a list of the last five faults in chronological order. The most
recent fault appears in first place (G13.2). Each time that a fault
occurs the drive shows the fault in general screen (G13.1). After the
fault is solved and reset, this fault will be shifted to the first position
of fault register (G13.2). The previous faults will shift down one
position. The oldest fault message (G13.6) will be lost.
Pressing
∗
key approx two seconds provides access to the
extended information that shows the order of fault:
FIFTH FAULT=Fxx up to FIRST FAULT=Fxx
The following table shows all the faults:
COD FAULT
COD FAULT
0
F0 NO FAULT
33
F33 SCR L3
1
F1 I LIM FLT
34
F34 IGBT TEMP
2
F2 V LIM FLT
35
F35 PHSE L1 LOSS
3
F3 PDINT FLT
36
F36 PHSE L2 LOSS
4
F4 U+DESAT
37
F37 PHSE L3 LOSS
5
F5 U-DESAT
40
F40 EXT / PTC
6
F6 V+DESAT
41
F41 COMMS TRIP
7
F7 V-DESAT
42
F42 AIN1 LOSS
8
F8 W+DESAT
43
F43 AIN2 LOSS
9
F9 W-DESAT
44
F44 CAL FLT
10
F10 NEG DESAT
45
F45 STOP T/O
11
F11 VIN LOSS
46
F46 EEPROM FLT
12
F12 IMB V IN
47
F47 COMMS T/O
13
F13 HI V IN
48
F48 SPI COM
14
F14 LW V IN
49
F49 SPD LIMIT
15
F15 CURL Vdc
50
F50 PSU FAULT
16
F16 HI Vdc
51
F51 SCR TEMP
17
F17 LW Vdc
52
F52 SUPPLY FAN
18
F18 IMB V OUT
53
F53 INTRNAL TEMP
19
F19 IMB I OUT
54
F54 WATCHDOG
TMR
20
F20 GROUND FLT
56
F56
EMERGEN.STOP
21
F21 I LIM T/O
57
F57 PUMP
OVERLOA
22
F22 TQ LIM T/O
65
F65 LOW
PRESSURE
25
F25 MTR O/L
66
F66 HI PRESSURE
27
F27 DL SMTH
67
F67 LOW WATER
28
F28 MICRO FLT
68
F68 CAVIT/UNDERL
29
F29 DSP FLT
69
F69 FLOW SWITCH
30
F30 WATCHDOG
70
F70 IRRIGATOR FL
31
F31 SCR L1
71
F71 CYCLING
32
F32 SCR L2
72
F72 IN PRES SW
-
7 CLEAR FAULTS=N G13.7
/ Erase
fault history
N
Y
N
OPT
FUNCTION
N=NO Function
disabled.
Y=YES
It erases fault history (last five faults). The screen
returns to default value ‘NO’, after all the faults
have been erased.
YES