SDRIVE 700
POWER ELECTRONICS
46
DESCRIPTION OF PROGRAMMING PARAMETERS
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
3 PSW ERR=XXXX
G1.2b
/ Unlock
password
recovery
0000 – 9999
0000
To recover the password the following formula can be used:
Unlock password = (XXXX/2)-3.
YES
4 LANG=ESPANOL
G1.4
/ Language
selection
ENGLISH
ESPANOL
DEUTSCH
ESPANOL It allows selection of the user language.
NO
5 INITIALISE=0
G1.5
/ Parameter
initialize
0 – 3
0
It allows selection of the parameters that we desire to initialize back
to the factory default value.
OPC.
DESCRIPTION
FUNCTION
0
NO INIT
None of parameters is initialized.
1 USR
PRMTR User parameters are only
initialized.
2
MTR PRMTR
Motor data are only initialized.
3 ALL
PRMTR All parameters of the drive are
initialized.
NO
6 SHORT Menu=NO
G1.6
/ To hide
some
configuration
menus
NO
YES
NO
If it is active, then configuration menus will not be accessible. Only
visible G1 OPTIONS MENU, G10 LIMITS, and Display groups.
NO
7 PROG= STANDAR G1.7
/ Program
activation
STANDARD
PUMP
STANDARD
It allows selection additional functionalities. If PUMP is selected,
then extended functionality for pumping control G25 will appear as
available.
The group G25 will be hidden if the pump program is not active.
Once selected the pump program, a character will appear in the
upper line of the display, beside the drive status, indicating
constantly that the pump program is active. The letter “b” in Spanish
and the letter “p” for English / German.
The most of parameters relative to the pump control are located in
Group 25, excepting those setting relatives to inputs and outputs
that can be found in groups G4 and G7.
Additionally there are some visualization screens included in
visualization groups SV.5 and SV.8.
NO
10.1.1.
Subgroup 1.10 – S1.10: Eloader (EEPROM loader)
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
UPLOAD=N
G1.10.1
/ Save
parameters from
drive to display
N
Y
N
When this parameter is set to ‘Yes’, parameters start to be copied
from drive to display automatically saving the drive configuration. A
message of the load status appears during the process:
UPLOADING….100%
When the load process is finished, the message above disappears
and the parameter will be displayed again. Set to ‘No’ as default
value.
NO
DOWNLOAD=N
G1.10.2
/ Save
parameters from
display to drive
N
Y
N
When this parameter is set to ‘Yes’, it copies the parameters from
display to drive automatically modifying and programming the
SD700. These parameters have been stored into display previously.
A message of the load status appears during the process:
DOWNLOADING….100%
When the load process is finished, the message above disappears
and the parameter will be displayed again. Set to ‘No’ as default
value.
NO
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
11 FAN CTRL=FIXE
G1.11
/ Drive fan
control mode
FIXE
TEMP
FIXE
It allows selecting the operation mode for drive fans.
OPTIO
FUNCTION
FIXE
The fans of the drive are connected with the start
command and they are disconnected after 3
minutes once the drive is stopped.
TEMP
The fans are connected at 51ºC and they are
disconnected when temperature is under 47ºC.
SI