SDRIVE 700
POWER ELECTRONICS
54
DESCRIPTION OF PROGRAMMING PARAMETERS
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
14 AIN1 LOSS=N
G4.2.14
/
Protection for
Analogue Input 1
loss
N
Y
N
To set the drive stop mode when a loss of the analogue input 1
signal occurs.
OPTION
FUNCTION
N=NO Function
disabled.
Y=YES
When the analogue input level decreases down
to zero value, sensor will be considered damaged
and the drive will stop generating a fault 'F42
AIN1 LOSS'.
YES
15 1_Z BAND=OFF
AIN1 ZERO BAND
G4.2.15
/ Zero
band filter for
Analogue Input 1
OFF=0.0 to
9.9%
OFF
Filtering of analogue input 1 signal. Setting this value we can filter
analogue input 1 to avoid possible electrical noise preventing the
analogue reading a zero value.
YES
10.4.3.
Subgroup 4.3 – S4.3: Analogue Input 2
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
1 SENSOR 2 ?=N
G4.3.1
/ Sensor
of Analogue
Input 2 enable
N
Y
N
It allows user to configure analogue input 2 for use with a sensor
and activates the parameters which are necessary to set it up. See
G4.3.2 up to G4.3.7.
OPTION
FUNCTION
N=NO
The analogue input will remained scaled in
defaults units (%).
Y=YES
The analogue input and any variables relating to
the analogue input, will be configured in the
engineering units selected in G4.3.2.
NO
2 SENSOR 2=Bar
4
G4.3.2
/
Selection of
sensor 2 units
%
l/s
m³/s
l/m
m³/m
l/h
m³/h
m/s
m/m
m/h
Bar
kPa
Psi
m
ºC
ºF
ºK
Bar
It allows selection of different units of measurement for the analogue
input 2 according to the sensor that is used.
If this parameter is modified, the minimum and maximum values of
the sensor range must be adjusted to ensure correct configuration.
Therefore, the following set values should be checked:
'G4.3.5 Smi2=+0.0Bar'
Î
Minimum range of sensor.
'G4.3.7 Sma2=+10.0Bar'
Î
Maximum range of sensor.
NO
3 AIN2 FORMAT=mA
G4.3.3
/
Analogue Input 2
format
V
mA
mA
It allows configuration of the analogue input 2 format for either a
voltage or current signal. Set according to the sensor that will be
used.
NO
4 4Ma
AIN2 LOW RANGE
G4.3.4
/
Minimum range
Analogue Input 2
-10 to +10V
+0 to +20mA
+4mA
It determines the minimum voltage or current value for analogue
input 2. Set according to the characteristics of the sensor that will be
connected.
YES
5 Smi2=+0.0Bar
4
SENS2 LOW RANGE
G4.3.5
/
Minimum range
of sensor 2
-3200 to
Sma2
(G4.3.7)
Engineering
units
+0.0Bar
It sets the minimum units value of the sensor connected to the
analogue input 2. This value should also correspond to the minimum
voltage or current level of the sensor set in 'G4.3.4 INmin2'.
Note:
This value should be checked if the units are changed in
'G4.3.2 SENSOR 2'. It will be set to operate in open loop and close
loop.
YES
6 20Ma
AIN2 HIGH RANGE
G4.3.6
/
Maximum range
Analogue Input 2
-10 to +10V
+0 to +20mA
+20mA
It determines the maximum voltage or current value for the
analogue input 2. Set according to the characteristics of the sensor
that will be connected.
YES
7 Sma2=+10.0Bar
4
SENS2 HIGH RANGE
G4.3.7
/
Maximum range
of sensor 2
Smi2
(G4.3.5) to
+3200
Engineering
units
+10.0Bar
It sets the maximum units value of the sensor connected to the
analogue input 2. This value should also correspond to the
maximum voltage or current level of the sensor set in 'G4.3.6
INmax2'.
Note:
This value should be checked if the units are changed in
'G4.3.2 SENSOR 2'. It is necessary to set this value in open loop
and close loop configurations.
YES
4
It will be available in case of 'G4.3.1 SENSOR 2 = Y'.