15.2
PEAK ( peak value memory )
Maximum input value x
max
and minimum input value x
min
are determined, stored and output at
Max
and
Min
. With
the stop input set to 1, the extreme values determined last remain unchanged.
If the
reset
input is set to 1, the extreme value memory and any applied
stop
command are cancelled. (x
max
and x
min
are
set to the instantaneous x1 value and follow input x1, until the
reset
input returns to 0.)
Unused inputs are interpreted as 0 or logic 0.
The function has a ‘memory’. This means: after power-on, it continues operating with the Min- and Max values which
existed at power-off, provided that the RAM data are still unchanged.
No parameters!
Inputs/outputs
Digital inputs
stop
With the stop input set to 1, instantaneous values Max and Min are unchanged.
reset
The reset input deletes the
Min
and
Max
values.
Analog inputs
x1
Process value, the min and max values of which are output.
Analog outputs
Max
Maximum value
Min
Minimum value
Selecting and storage
9499 040 50611
PEAK ( peak value memory )
86
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...