10
Non-linear functions
10.1
GAP (dead band)
y
x
L
1
1
= -
bei x1 < L
y
1
0
=
bei x1 = L...H
y
x
H
1
1
= -
bei x1 > H
The range of the dead band is adjusted with parameters Low (lower limit) and High (upper limit). If input value
x1
is
within the dead band (Low
ß
x1
ß
High), output value
y1
= 0. If
x1
is not used, this is interpreted as
x1
= 0.
Example:
In the following example, -10 for
Low
and 50 for
High
was used.
Input
x1
Output
y1
Parameter
Description
Range
Default
Low
Lower limit value
-29 999...999 999
0
High
Upper limit value
-29 999...999 999
0
9499 040 50611
Non-linear functions
37
GAP (dead band)
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...