Parameter
Description
Value
Default
x1a in
Measured value correction Inp_a, P1 input value
Real
0
x1aOut
Measured value correction Inp_a, P1 output value
0
x2a in
Measured value correction Inp_a, P2 input value
100
x2aOut
Measured value correction Inp_a, P2 output value
100
x1b in
Measured value correction Inp_b, P1 input value
0
x1bOut
Measured value correction Inp_b, P1 output value
0
x2b in
Measured value correction Inp_b, P2 input value
100
x2bOut
Measured value correction Inp_b, P2 output value
100
Configuration
Description
Value
Default
Typ_a
Voltage 0...10V
0
0
Voltage -50...1500mV
1
Fail_a
Switched off
0
1
Upscale, Inp_a = x100_a
1
Downscale, Inp_a = x0_a
2
Substitute value, Inp_a = XaFail
3
Xakorr
Measured value correction Inp_a switched off
0
0
Measured value correction Inp_a effective
1
Typ_b
Voltage 0...10V
0
0
Voltage -50...1500mV
1
Fail_b
Switched off
0
1
Upscale, Inp_b = x100_b
1
Downscale, Inp_b= x0_b
2
Substitute value, Inp_b = XbFail
3
Xbkorr
Measured value correction Inp_b switched off
0
0
Measured value correction Inp_b effective
1
a0_a
Physical value Inp_a at 0%
Real
0
x100_a
Physical value Inp_a at 100%
Real
100
XaFail
Substitute value with sensor error at Inp_a
Real
0
Tfm_a
Filter time constant of Inp_a in seconds
Real
0,5
x0_b
Physical value Inp_b at 0%
Real
0
x100_b
Physical value Inp_b at 100%
Real
100
XbFail
Substitute value with sensor error at Inp_b
Real
0
Tfm_b
Filter time constant of Inp_b in seconds
Real
0,5
9499 040 50611
Modular I/O - extension-modules
233
U_INP (analog input card -50...1500mV, 0...10V)
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...