16.4
VELO ( rate-of-change limiting)
The function passes input variable x1 to output y1 and limits its rate of change dx1/dt to a positive and negative gradi-
ent.
The gradients can be adjusted either as parameter
GrX
+ and
Grx-
or preset at analog inputs
GrX
+ and
Grx-
.
Switch-over between the gradient sources is by parameter
Mode
+ for the positive gradient and by
Mode-
for the
negative gradient.
Via digital inputs d1 and d2, limiting can be switched off separately for positive and negative rates of change.
When using the analog inputs for gradient adjustment, the following is applicable:
GrX
+
?
0 or
GrX-
ß
0 otherwise the relevant gradient is set to 0.
a
The function has a ‘memory’. This means: after power-on, it continues operating with the value of y1 which
existed at power-off, provided that the RAM data are still unchanged.
Inputs/outputs
Digital inputs
d1
Control of positive gradient 0 = the selected gradient is effective. 1= gradient =
Î
d2
Control of negative gradient 0 = the selected gradient is effective. 1= gradient = -
Î
Analog inputs
x1
Input variable to be limited
GrX+
positive gradient [
1
/s
] with parameter Mode+
=
Inp. GrX+
GrX-
negative gradient [
1
/
s
] with parameter Mode-
=
Inp. GrX-
Analog output
y1
Limited input value
x1
No configuration parameters!
Parameters
:
Parameter
Description
Range
Default
Mode+
Source of positive gradient
parameter
GrX+
Para.GrX+
t
analog input
GrX+
Inp. GrX+
Mode-
Source of negative gradient
parameter
GrX-
Para.GrX-
t
analog input
GrX-
Inp. GrX-
Grx+
positive gradient [
1
/
s
] with parameter
Mode
+ =
Para.GrX+
0 ... 999 999
0
Grx-
negative gradient [
1
/
s
] with parameter
Mode-
=
Para.GrX-
-29 999 ... 0
0
Limit value signalling and limiting
9499 040 50611
VELO ( rate-of-change limiting)
102
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...