Override (limiting) control
using a three-point
stepping output
Override control is also possible by
means of a classical three-point
stepping controller. The positioning
signals of the limiting controller
must be connected as shown in the
example Fig.: 23.
Which one of the two controllers in-
fluences the process is decided in
the slave controller logic. The first
“close” pulse coming from the limit-
ing controller switches over to over-
ride control. The limited controller
automatically retrieves the position-
ing authority, when it first tries to
close the actuator further.
Bumpless auto/manual switch-over
Sudden process interventions by control mode switch-over are usually not desired. Excepted is purposeful switch-over y
r
Y2.
A
r
M switch-over is always bumpless; the last correcting value is frozen and can be changed manually. M
r
A
switch-over is different. Correcting value differences are compensated as follows: when switching over, the controller
integral action is set to correcting value Y
M
output last plus correcting variable portions of the controller P and D action
running in the background
(Y
I
= Y
M
+ Y
PD
). Now, only the integrator, which adapts the correcting variable slowly to the stationary value according
to the actual control deviation, is active. Until the D action has decayed completely, the adaptation can be delayed or
accelerated
9499 040 50611
Controller
201
Process value calculation
M
Limitation
controller
OPEN
CLOSE
positioner
e.g. flow
e.g. pressure
repeater
reply
Fig.:23 Override control using 3-point stepping controllers
A r M
Time
correcting value y
M r A
upper correcting value limit y+
lower correcting value limit y-
Manual
AUTOMATIC
AUTOMATIC
Y
I
Ypid
Y
M
Ypid
Y = Y
- Y
I
M
PD
Automatic-
mode Y
PD
Fig.:24
Bumpless switchover
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...