15.10
SELV2 ( cascadable selection of variables )
Dependent of input Select,, one of the four inputs x1...x4 is connected with output y1.
Unused inputs are interpreted as 0.
Output
Casc
= input
Select
-3.
The function can be cascaded as shown in the example given below. Dependent of input signal
Select
at the 1st
SELV1, the corresponding variable is output at
Y1
of the 2nd SELV2.
SELV1
y 1
output 2nd SELV1
Select
< 1,5
x1
of 1st SELV1
1,5 <
Select
< 2,5
x2
of 1st SELV1
2,5 <
Select
<3,5
x3
of 1st SELV1
3,5 <
Select
< 4,5
x4
of 1st SELV1
4,5 <
Select
< 5,5
x2
of 2nd SELV1
5,5 <
Select
< 6,5
x3
of 2nd SELV1
< 6,5
x4
of 2nd SELV1
Inputs/outputs
Analog inputs
x1
Input is output at y1 with
Select
< 1,5.
x2
Input is output at y1 with 1,5 <
Select
< 2,5.
x3
Input is output at y1 with 2,5 <
Select
< 3,5.
x4
Input is output at y1 with
Select
< 3,5.
Select
Dependent of input value, the relevant variable is output at
y1
.
Analog outputs
y1
According to the input value of
Select
, the relevant input variable is output.
Casc2
Cascade output =
Select
- 3
No parameters!
Selecting and storage
9499 040 50611
SELV2 ( cascadable selection of variables )
96
Cascading
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...