Digital outputs:
z1
...
z6
The outputs provide a status, which shows if the last storage of the values taken over from the
inputs was successful (z1 ... z6 = 0). Errors may occur due to exceeded limits of the parameter
value or due to non-existing parameters (z1 ... z6 = 1).
Analog inputs:
x1
...
x6
Process values to be stored as parameter values (default = 0)
Analog outputs:
y1
...
y6
The values of the 6 parameters are output at the analog outputs. Unused parameters provide value
`0’.
Parameter and configuration data
Configuration
Description
Values
Default
B
l
ock1
...
Block6
Block number of parameter to be displayed
*
*
Num1
...
Num6
Parameter number
*
*
* To avoid confusions and thus operating errors, we recommend adjusting block numbers and parameters exclusively
via the engineering tool, where the parameters with their short-form descriptions must also be specified. Text entry is
only possible via the engineering tool.
Entry and display of texts
Changing the texts displayed in the unit is possible only in the engineering tool! Max. 16 characters can be entered in
each text parameter. Dependent of whether a line is allocated to a block number or defined as a text line, all characters
(
Blockx
=
Text
) or only the first 6 characters (
Blockx
=
#xxx
) are displayed in the unit. If parameter num-
ber (
Numx
) or block number (
Blockx
) are undefined, `
??????
‘ is displayed as a value.
Parameter allocation to the display lines:
Block1; Num1; Text1; Unit 1
r
line 1
....
Block6; Num6; Text6; Unit6
r
line 6
The following values or texts are displayed:
Header
Ü
Block number 3 digits
*
Fixed text or spaces (no access)
Ö
The first 16 characters of ‘title’
ä
Parameter name (the first 6 characters of
‘Text 1’...’Text 6’ dependent of line)
Parameter line
#
the parameter values
<
Unit (the first 6 characters of
‘Unit 1’...’Unit 6’ dependent of line)
Text line
>
The first 16 characters of
‘Text 1’...’Text 6’ dependent of line
VPARA operating page
VPARA has an operating page, which can be selected in the operating
menu with input ‘
hide
‘ not used.
For changing the value of an input field, this value must be marked
with
ID
(inverse display). When acknowledging the value with
M
, it
starts blinking and can be adjusted with
ID
.
When reaching the required value, confirm it with
M
.
If the analog inputs (
x1
...
x6
) are used by the engineering, operation
(change) of this input field is not possible.
Visualization
9499 040 50611
VPARA ( parameter operation )
110
:
Ü
*
Ö
=
ä
#
<
*
*
>
*
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...