25.2
AINP3...AINP5 ( analog inputs 3...5 )
For standard signal connection
General
Functions ‘AINP3...AINP5’ are used for configuration and parameter setting of analog inputs INP3...INP5. They are
firmly allocated to block number 63...65 and are calculated in each time slot. The functions provide corrected measure-
ment values and measurement value statuses at their outputs.
Inputs / outputs
Digital outputs:
fail
Signals an input error (short-circuit, wrong polarity, ..)
Analog outputs:
Inp1
Signal input
Parameter and configuration data
Parameter
Description
Values
Default
x1in
Measured value correction P1, input
-29999 ... 999 999
0
x1out
Measured value correction P1, output
-29999 ... 999 999
0
x2in
Measured value correction P2, input
-29999 ... 999 999
100
x2out
Measured value correction P2, output
-29999 ... 999 999
100
Configuration
Description
Values
Default
Type
0...20 mA
0...20mA
t
4...20 mA
4...20mA
0...10 V
0...10V
2...10 V
2...10V
Fail
Fail function off
disabled
t
Digital output
fail
= 1,
y1
=
x100
Upscale
Digital output
fail
= 1,
y1
=
x0
Downscale
Digital output
fail
= 1,
y1
=
XFail
Subst.val.
Xkorr
Measured value correction off
off
t
Measured value correction adjustable
on
x0
Physical value at 0%
effective only with standard signals
(0/4..20mA or 0/2..10V)
-29999 ... 999 999
0
x100
Physical value at 100%
-29999 ... 999 999
100
Tfm
Filter time constant [s]
0 ... 999 999
0,5
9499 040 50611
Inputs
209
AINP3...AINP5 ( analog inputs 3...5 )
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...