13.4
PULS (analog pulse conversion)
n
Puls
h
x
x
x
x
=
×
-
-
1
0
100
0
n =
x0 =
x100 =
x1
=
Number of pulses per hour
Parameter
Parameter
Analog input
Input variable x1 is converted into a number of pulses per hour. Parameter Puls/h is used for selecting the maximum
number of pulses at x1 ? x100. For x1 ß x0 no pulses are output.
Within range x0 - x100 , input value x1 is converted linearly into pulses per hour.
Puls/h
= maximum Pulse/h
x0
=
0% of Puls/h
x100
=
100% of Puls/h
The parameter settings result in a straight line between 0 and 3600 pulses /h according to input x1The pulse length
corresponds to the sampling interval (100, 200, 400 or 800ms) adjusted for this block. The length of switch-off time be-
tween pulses is not always equal and dependent of the configured sampling interval.
The sampling interval allocation also determines the maximum number of pulses/hour, which can be realized. If higher
values than can be output due to the sampling interval are entered in parameter Puls/h, limiting is to the maximum pos-
sible number of pulses.
Maximum number of pulses:
100 ms
=
18 000 pulses/h
200 ms
=
9 000 pulses/h
400 ms
=
4 500 pulses/h
800 ms
=
2 250 pulses/h
Signal converters
9499 040 50611
PULS (analog pulse conversion)
68
x1
n
x0
x100
Puls/h
0
n=Puls/h x1-x0
x100-x0
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...