Inputs/
outputs
Digital inputs:
hide
Display suppression (with
hide
= 1 the operating page is not displayed).
lock
Adjustment locking (with
lock
= 1 the values are not adjustable by means of keys
ID
).
inc
Increment for manual adjustment
dec
Decrement for manual adjustment
x f
Sensor error x1...x3
yp f
Sensor error Yp
a/m
0 = automatic 1 = manual
w/w2
0 = int./ext. set-point 1 = W2
we/wi
0 = external 1 = internal set-point
pi/p
0 = PI action;
1 = P action
1)
(
r
page PI/P switch-over) (not applicable to PIDMA)
d ovc+
1 = override c with 3-point stepping controller (
r
page 201 ff) (not applicable to PIDMA)
d ovc-
1 = override control - with 3-point stepping controller(
r
page 201ff) (not applicable to PIDMA)
track
0 = tracking function off; 1 = tracking function on(
r
y/y2
0 = output value Y1 = output value Y2
off
0 = controller switched on 1 = controller switched off
sm/hm
0 = soft manual 1 = hard manual
ostart
1 = self-tuning start
r
page 178
w stop
1 = effective set-point freeze
gr off
1 = set-point gradient suppression
rstart
1 = Start the set-point ramp
r
the set-point makes a step change towards the process value and
goes to the adjusted process value according to GRW+ (GRW-). The rising flank (0
r
1) is evaluated
.
o-hide
1 = self-tuning page display suppression
oplock
Blockage of key
H
(with
oplock
=
1, switchover to manual by means of key
H
is not possible).
Digital outputs:
y1
Status of switching output Y1; 0 = off 1 = on
y2
Status of switching output Y2; 0 = off 1 = on
c fail
1 = controller in error handling
off
0 = controller switched off 1 = controller switched on
a/m
0 = automatic 1 = manual
y/y2
0 = output value Y 1 = output value Y2
we/wi
0 = external 1 = internal set-point
pi/p
feedback/integrator 0 = with 1 = without (not applicable to PIDMA)
o run
Self-tuning running
o stab
Process at rest (for self-tuning) (not applicable to PIDMA)
o err
Error during self-tuning
xw sup
Alarm suppression with set-point change
Analog inputs:
x1
Main variable x1
x2
Auxiliary variable x2
e.g. for ratio control
x3
Auxiliary variable x3
e.g. for 3-element control
Wext
External set-point
OVC+
Override c
r
page 201
OVC-
Override control -
r
page 201
Yp
Position feedback
Yhm
Output with hard manual
Yadd
Feed-forward control
ParNo
Only with CONTR+; required parameter set
Controller
9499 040 50611
PIDMA
160
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...