29.6
U_OUT (analog output card 0/2...10V, +/-10V)
Analog output, plugs into modular options card C
For configuration and parameter setting of analog output
U_OUT
.
Output calculation is fixed to once per time slot.
Configuration
Description
Values
Default
Typ_a
0...10V
0
0
2...10V
1
+/-10V
2
x0_a
Physical value Inp_a at 0%
Real
0
x100_a
Physical value Inp_a at 100%
Real
100
Typ_b
0...10V
0
0
2...10V
1
+/-10V
2
x0_b
Physical value Inp_b at 0%
Real
0
x100_b
Physical value Inp_b at 100%
Real
100
Digital output:
slotid
0 = correct module fitted
1 = wrong module fitted
Analog inputs:
X_a
r
output value for channel a
X_b
r
output value for channel b
235
U_OUT (analog output card 0/2...10V, +/-10V)
U_OUT (analog output card 0/2...10V, +/-10V)
Modular I/O - extension-modules
H
ARDW
A
R
E
S
O
FTW
AR
E
+/- 10 V
0 ... 10 V
2 ... 10 V
OUT a
slotid
x0_a
x100_a
Typ_a
OUT b
x0_b
x100_b
Typ_b
+/- 10 V
0 ... 10 V
2 ... 10 V
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...