18.4
DPWRIT ( write level1 data via PROFIBUS )
General
Block numbers 11...14. The data of a PROFIBUS data channel are transmitted into the memory. Block number 11 trans-
mits the data of channel 1, block number 12 transmits the data of channel 2, etc. The PROFIBUS module writes the data
of two channels at intervals of 100ms. The data set comprises 6 analog process values (y1...y6) and 16 digital status
informations (z1...z16), which are available to the engineering. The digital outputs (b-err, p-err, c-err, d-err and valid) in-
dicate the PROFIBUS status.
g
Further information on communication with PROFIBUS is given in the interface description (order no.:
9499 940 52711).
Inputs/outputs
Digital outputs:
z1
...
z16
Digital process values, which can be written via the Profibus.
b-err
PROFIBUS status: 1 = bus access not successful
p-err
PROFIBUS status: 1 = faulty parameter setting
c-err
PROFIBUS status: 1 = faulty configuration
d-err
PROFIBUS status: 1 = no data communication
valid
PROFIBUS status: 1 = data o.k.
Analog outputs:
y1
...
y6
Analog process values, which can be written via the Profibus.
Communication
9499 040 50611
DPWRIT ( write level1 data via PROFIBUS )
116
z1
z16
...
y1
.
.
.
.
.
y6
Interface
(0)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
7 6 5 4 3 2 1 0
7 6 5 4 3 2 1 0
b-err
p-err
c-err
d-err
valid
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...