Parameter and configuration data
Configuration Description
Range
Default
MTyp
Module type
0: RM221-0 = 4 x 0/4...20 mA
1: RM221-1 = 4 x -10/0...10 V
2: RM221-2 = 2 x 0/4...20 mA + 2 x -10/0...10 V
3: RM222-0 = 4 x 0/4...20 mA, TPS
4: RM222-1 = 4 x -10/0...10 V, potentiometer, TPS
5: RM222-2 = 2 x 0/4...20 mA + 2 x -10/0...10 V, potentiometer, TPS
6: RM224-1 = 4 x TC/Pt100, 16 bits
7: RM224-0 = 2 x TC, 16 bits
8: RM224-2 = 1 x -3...3V, 1x TC, 16 bits
STyp 1
...
STyp 4
Input signal
1: type J
= -120 ... 1200°C
2: type K
= -130 ... 1370°C
3: type L
= -120 ... 900°C
4: type E
= -130 ... 1000°C
5: type T
= -130 ... 400°C
6: type S
= 12 ... 1760°C
7: type R
= 13 ... 1760°C
8: type B
= 50 ... 1820°C
9: type N
= -109 ... 1300°C
10: type W
= 50 ... 2300°C
30: Pt100
= -200 ... 850°C
40: standard signal = 0 ... 10V
41: standard signal = -10 ... 10V
50: standard signal = 4 ... 20mA
51: standard signal = 0 ... 20mA
Unit 1
Temperature unit input 1 to 4
(only relevant with thermo-
couple and Pt100 inputs)
0: unit = °C
0
...
1: unit = °F
Unit 4
2: unit = K
Tf 1
Filter time constant input 1 ...
4 in (s)
0 ... 999 999
0,5
...
Tf 4
x0 1
Scaling start value input
1...input 4
-29 999 ... 999 999
0
...
x0 4
x100 1
...
x100 4
Scaling end value input 1 ...
input 4
-29 999 ... 999 999
100
Fail 1
...
Fail 4
Signal behaviour with sensor
error at input 1...4
upscale
downscale
t
X1in
1...4
Measured value correction
input value Segment point 1
r
input 1...4
-29 999 ... 999 999
0
X1out
1...4
Measured value correction
output value Segment 1
r
input 1...4
-29 999 ... 999 999
0
X2in
1...4
Measured value correction
input value Segment point 2
r
input 1...4
-29 999 ... 999 999
100
X2out
1...4
Measured value correction
output value Segment point 2
r
input 1...4
-29 999 ... 999 999
100
9499 040 50611
KS98+ I/O extensions with CANopen
123
RM_AI (RM200 - analog input module)
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...