Controlling the set-point
The digital input
rstart
reacts to a positive signal slope and sets the effective set-point to the process value. The
new goal set-point is started on the basis of the controlled variable
xeff
.
Such a ramp can only be started with activated gradient function (
Grw
+,
Grw
-,
Grw2
and digital input
gr
_
off
not set). The digital input
w
_
stop
freezes the effective set-point Weff , i.e., the effective set-point is
held to the current value, even if the effective set-point straight approaches a new goal set-point or a new goal
set-point is selected.
Set-point tracking
During the change-over of
Wext
r
W
it can come to unwanted set-point jumps. To aviod these jumps set-point
tracking exists.
Set-point tracking takes care that in switch-over of
Wext
r
W
, the past
Wext
is taken over as int. set-point
W
.
When shifting back (
W
r
Wext
)
Wext
is started with the attitude of
Grw+/-
. If the controller shall follow pro-
cess value or set-point tracking is determined with the configurationword
Wtrac
. Tracking can be activated via in-
terface or digital input
track
.Tracking is evaluated with priority.
a
If in a place (interface or digital input) is switched to tracking, switching in another place is not possible!
9499 040 50611
Controller
193
Set-point functions
set-point2
set-point1
Adjustment of
r
set-point1
set-point2
rstart
=
z
w_stop
= 1
w_stop
= 0
gr_off
= 1
upper set-point limit W100
effective set-point
x
W
Time
Set-points, process value
process value
Grw+
lower set-point limit W0
Fig.: 14
Effect of control inputs (
rstart, w-stop
und
gr_off
) on the set-point
set-point2
set-point1
Adjustment of
r
set-point1
set-point2
rstart
=
z
w_stop
= 1
w_stop
= 0
gr_off
= 1
upper set-point limit W100
effective set-point
x
W
Time
Set-points, process value
process value
Grw+
lower set-point limit W0
Fig.: 15
Set-point tracking with switch-over to internal set-point
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...