Example 1:
Zero offset
x1in
= 100
x1out
= 100 + 1,5
x2in
= 300
x2out
= 300 + 1,5
The corrected values are shifted evenly with reference to
the input values over the complete range.
Example 2:
Gain change (rotation around the coordinate origin)
x1in
=
0
x1out
=
0
x2in
= 300
x2out
= 300 + 1,5
The corrected values diverge despite equality with
the input values at
x1in
and
x1out
.
Example 3:
Zero and gain matching
x1in
= 100
x1out
= 100 - 2,0
x2in
= 300
x2out
= 300 + 1,5
The corrected values are already shifted at input
values
x1in
and
x1out
and diverge additionally.
Sensor types
The input sensor type can be defined as potentiometric transducer or as standard current signal.
Potentiometric transducer
Overall resistance
ß
1000
[
incl. 2
w
RL.
Calibration or scaling are with the sensor connected.
+
Before calibration, the mains frequency required during operation must be adjusted.
Main menu
r
Miscellaneous
r
Device data
r
Freque
.
Calibration is as follows.
Transducer calibration is possible via interface and front-panel operation.
Select
set 0%
as shown in Fig.: 26. After pressing the selector key,
set 0%
starts blinking. Bring the transducer
into the position corresponding to X0 (usually lower end position). The instantaneously valid value for INP6 is displayed
‘
X
‘. Press the selector key again to store this actual value as X
0
.
Select
set 100%
. After pressing the selector key
set 100%
starts blinking. Now, bring the transducer into the
position corresponding to X
100
(mostly upper end position). The instantaneously valid value for INP6 is displayed ‘
X
‘.
Press the selector key again to store this actual value as X
100
.
Inputs
9499 040 50611
AINP6 ( analog input 6 )
212
corrected
characteristic
corrected
characteristic
corrected
characteristic
input
characteristic
input
characteristic
input
characteristic
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...