19.8
RM_DMS strain gauge module
Function RM_DMS reads data from a special strain gauge module of KS98+ I/O extension with CANopen. Max. 2 strain
gauges can be connected to the module. The measured values are available at outputs AI 1 and AI 2.
The two measurements can be influenced via digital command inputs, e.g. zero setting. Monitoring a new command (
positive flank at one of the digital inputs ) is restarted only when the “ready” output is “1”. The module position in the
RM rack is determined by connection of analog input Slotx to the RM2xx node.
a
Important hint:
A special coupler module ( RM201-1 ) must be used for operation of the strain gauge module. This coupler module can-
not be combined with thermocouple modules. Moreover, the limitations as for coupler module RM201 (e.g. max. 4 ana-
log input modules) are applicable.
Digital inputs:
q
set_t1
Set tare strain gauge channel 1. The actual weight is not stored
continuously as tare (packaging weight). The following measurements provide the net
weight.
q
res_t1
Reset tare strain gauge channel 1. The tare value is set to 0.
Gross weight= net weight.
q
zero_1
Zero setting of strain gauge channel 1 measured value. The actual
measured value is stored as a zero value in a non-volatile memory.
q
set_t2
Set tare strain gauge channel 2. The actual weight is buffered as tare
(packaging weight). The following measurements provide net weight.
q
res_t2
Reset tare strain gauge channel 2. The tare value is set to 0.
Gross weight=net weight.
q
zero_2
Zero setting of the strain gauge channel 2 measured value. The actual
measured value is stored as zero in the non-volatile memory..
KS98+ I/O extensions with CANopen
RM_DMS strain gauge module
9499 040 50611
126
Содержание KS 98
Страница 8: ...Description 9499 040 50611 Construction 8...
Страница 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Страница 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Страница 14: ...Front view 9499 040 50611 14...
Страница 16: ...Mounting 9499 040 50611 16...
Страница 26: ...Maintenance 9499 040 50611 Further information 26...
Страница 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Страница 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Страница 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Страница 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Страница 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Страница 202: ...Controller 9499 040 50611 Process value calculation 202...