5-20
Functions
5
5.7.3
Auto Conversion and Clear Functions When Changing Simplified Scaling
Weighted Data
When simplified scaling weighted data is changed, the following parameters are automatically converted:
[Related parameters]
#9
Feeding velocity
#10
Jog velocity
#11
Over-travel search velocity during a homing move
#12
Homing operation: Home sensor proximity signal search velocity
#13
Homing operation: Home sensing feed velocity 1
#15
Homing operation: Origin position offset move feed velocity
#29
Offset distance from the Home position
#31
Operation width under testing mode
#32
Operation width under Auto-tuning
#58
Positioning setting width
#45
Positioning setting width2
#46
Positioning setting width3
#47
Positioning setting width4
#213 Maximum velocity
5.7.4
Limiting the Maximum Parameter Values
Limit processing is performed for the following parameters related to velocity at the time of parameter entry and
when the power is turned ON.
[Related parameters]
#9
Feeding velocity
#10
Jog velocity
#11
Over-travel search velocity during a homing move
#12
Homing operation: Home sensor proximity signal search velocity
#13
Homing operation: Home sensing feed velocity1
#15
Homing operation: Origin position offset move feed velocity
[At the time of parameter entry]
If a parameter value exceeds #357
Maximum velocity monitor value
when it is set by the user, it will be
processed as out of range data. However, limit processing is not performed in the hold-on state (while
downloading parameters), when changing the simplified scaling weighted data, or when changing the maximum
velocity data.
[When the power is turned ON]
During processing when the power is turned ON after simplified scaling weighted data or maximum velocity
data is changed, a limit is applied using the value equivalent to the
#357
Maximum velocity
monitor that is
successively initialized.
Содержание Dynaserv G2
Страница 1: ...Effective March 1 2002 p n 88 020389 01 A Automation Dynaserv G2 Drive User Guide ...
Страница 22: ...2 1 Chapter 2 Installation 2 1 Installation of the Motor 2 2 Installation of the Driver ...
Страница 146: ...11 11 3 Driver Section 1 U A B 500W Type B is shown in the figure 2 U L 2kW level without regenerative unit 11 ...
Страница 147: ...11 12 Specifications 11 3 U K 2kW level with regenerative unit ...