70
Analog monitor selection
Always
Minimum value:
0
Maximum value:
5
Initial value:
4
Unit:
None
Long:
Short:
AnalogMonitorSelect
A_MonSel
Select the content to be output to the analog monitor.
0: Position deviation [pulse]
1: Test operation response [pulse]
2: Position command value [pulse]
3: Current position value [pulse]
4: Position command differential value (command velocity) [pps]
5: Current position differential value (current velocity) [pps]
71
Axis positioning error monitoring gain (analog monitor)
Always
Minimum value:
0
Maximum value:
8
Initial value:
0
Unit:
None
Long:
Short:
PerrMonitorGain
PerrMon_G
Specify the position deviation monitoring gain of the analog monitor.
0: 6.55V / 32768 pulses
1: 6.55V / 16384 pulses
2: 6.55V / 8192 pulses
3: 6.55V / 4096 pulses
4: 6.55V / 2048 pulses
5: 6.55V / 1024 pulses
6: 6.55V / 512 pulses
7: 6.55V / 256 pulses
8: 6.55V/ 128 pulses
72
Test operation monitoring gain (analog monitor)
Always
Minimum value:
0
Maximum value:
8
Initial value:
0
Unit:
None
Long:
Short:
TestMonitorGain
PerrMon_G
Specify the test operation response monitoring gain of the analog monitor.
0: 6.55V / 32768 pulses
1: 6.55V / 16384 pulses
2: 6.55V / 8192 pulses
3: 6.55V / 4096 pulses
4: 6.55V / 2048 pulses
5: 6.55V / 1024 pulses
6: 6.55V / 512 pulses
7: 6.55V / 256 pulses
8: 6.55V/ 128 pulses
Содержание Dynaserv G2
Страница 1: ...Effective March 1 2002 p n 88 020389 01 A Automation Dynaserv G2 Drive User Guide ...
Страница 22: ...2 1 Chapter 2 Installation 2 1 Installation of the Motor 2 2 Installation of the Driver ...
Страница 146: ...11 11 3 Driver Section 1 U A B 500W Type B is shown in the figure 2 U L 2kW level without regenerative unit 11 ...
Страница 147: ...11 12 Specifications 11 3 U K 2kW level with regenerative unit ...