Error number
20
Power module error
Error type:
[KIND_RGR] Always error
Measures:
[TYPE_SRV] Servo OFF
Long:
Short:
PowerModuleError
PwrMdlErr
Main cause:
A power module error in the driver was detected.
[Subcode]
1: Over-voltage (over-voltage of main power supply)
2: Over-current (over-current detected, 1 PM fault)
Action to take:
Error number
21
AC power error
Error type:
[KIND_SRV] Servo error
Measures:
[TYPE_SRV] Servo OFF
Long:
Short:
AC_PowerError
AC_PwrErr
Main cause:
Either the main power supply is not input or the input voltage has not reached the rating level.
Action to take:
Verify the main power supply.
Error number
22
Over load
Error type:
[KIND_RGR] Always error
Measures:
[TYPE_ELS] Others
Long:
Short:
Overload
Overload
Main cause:
The motor use is overloaded.
[Subcode]
1: The motor is overheated.
2: The power module heat sink is overheated.
Action to take:
Error number
23
Excessive position deviation
Error type:
[KIND_SRV] Servo error
Measures:
[TYPE_ELS] Others
Long:
Short:
OverPerr
OverPerr
Main cause:
The position deviation was greater than the tolerance.
Action to take:
Perform the servo adjustment again. If an error still occurs, extend the tolerance.
Error number
24
Over speed
Error type:
[KIND_RGR] Always error
Measures:
[TYPE_ELS] Others
Long:
Short:
OverSpeed
OverSpeed
Main cause:
The velocity was higher than the maximum velocity.
Action to take:
Содержание Dynaserv G2
Страница 1: ...Effective March 1 2002 p n 88 020389 01 A Automation Dynaserv G2 Drive User Guide ...
Страница 22: ...2 1 Chapter 2 Installation 2 1 Installation of the Motor 2 2 Installation of the Driver ...
Страница 146: ...11 11 3 Driver Section 1 U A B 500W Type B is shown in the figure 2 U L 2kW level without regenerative unit 11 ...
Страница 147: ...11 12 Specifications 11 3 U K 2kW level with regenerative unit ...