1-32
1
1
NOTE
<Type E1>
(1) Refer to “Recommended Wire Length and Wire
Diameter for Power Supply System” for the explanation
of “A”, “B”, “C” and “D” in the above diagrams.
(2) The basic connection diagram of the indoor unit
shows the 7P terminal board, so the terminal boards
in your equipment may differ from the diagram.
(3) Refrigerant Circuit (R.C.) address should be set
before turning the power on.
(4) Regarding R.C. address setting, refer to the installation
instructions supplied with the outdoor unit. Auto address
setting can be executed by remote controller automatically.
Refer to the installation instructions supplied with the
remote controller (optional).
Power
supply
Inter-unit
control
wiring
L
N
U1
U2
R1
R2
7P terminal board
Type E1
Remote
control
wiring
L2
L1
U2
U1
L3
N
A
L1
L2
L3
N
U2
U1
L
N
1
2
2
1
D
B
L
N
2
1
C
Power supply*
220 – 240 V ~50/60 Hz
Remote
controller
WHT
BLK
* Regarding S-250PE1E8, the power supply is
220-240V, 50Hz only.
Ground
Ground
Ground
Outdoor unit (3-phase)
INV unit
Power supply
380 – 415 V, 3N, ~ 50/60 Hz
Indoor
unit
CAUTION
(1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug
(CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units
except any one of the outdoor units. (When shipping: In shorted condition.)
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 1-5)
(3) Use shielded wires for inter-unit control wiring (c) and
ground the shield on both sides, otherwise misoperation
from noise my occur. (Fig. 1-6)
Connect wiring as shown in Wiring System Diagram.”
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Prohibited
Prohibited
Indoor unit
Fig. 1-5
Fig. 1-6
Shielded wire
Ground
Ground
(4) Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed
5 or 3 *1.5 mm
2
flexible cord. Type designation 60245 IEC 57 (H05RN-F, GP85PCP etc.) or heavier cord.
Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to
CENELEC (HAR) rating specifications) or use the cables based on IEC standard. (60245 IEC57, 60245
IEC66)
Loose wiring may cause the terminal to overheat or result in unit malfunction.
A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, follow the instructions on “How to connect wiring to the terminal”
and fasten the wire securely with the fixing screw of the terminal plate.
WARNING
Fig. 1-8
Fig. 1-7
How to connect wiring to the terminal
For stranded wiring
(1)
(2)
(3)
(4)
Cut the wire end with cutting pliers, then strip the
insulation to expose the stranded wiring about
10 mm and tightly twist the wire ends. (Fig. 1-7)
Using a Phillips head screwdriver, remove the
terminal screw(s) on the terminal plate.
Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring pressure
terminal.
Place the ring pressure terminal, and replace and
tighten the removed terminal screw using a
screwdriver. (Fig. 1-8)
Insulation tape
8mm
Insulation tape
Shield mesh
Shield mesh
Fig. 1-9
Fig. 1-10
Fig. 1-11
Fig. 1-12
Examples of shield wires
(1)
(2)
(3)
(4)
Remove cable coat not to scratch braided shield. (Fig. 1-9)
Unbraid the braided shield carefully and twist the
unbraided shield wires tightly together. Insulate the shield
wires by covering them with an insulation tube or wrapping
insulation tape around them. (Fig. 1-10)
Remove coat of signal wire. (Fig. 1-11)
Attach ring pressure terminals to the signal wires and
the shield wires insulated in Step (2). (Fig. 1-12)
Screw and
Special washer
Ring
pressure
terminal
Terminal plate
Ring pressure
terminal
Screw
Special
washer
Wire
Wire
Ring
pressure
terminal
Strip 10 mm
Stranded wire
Wiring sample
Outdoor Unit
1.
Earth
Use this screw when connecting to
ground for the Inter-unit control wiring.
Power Supply
Inter-unit Control Wiring
2.
Earth
Use this screw when connecting to
ground for the Inter-unit control wiring.
Power Supply
Inter-unit Control Wiring
3.
Earth
Use this screw when connecting to
ground for the Inter-unit control wiring.
Clamper *
(Field supply)
* First remove the attached resin fixture.
Then lead the clamper (field supply) through
the screw hole and fix the power supply wire.
Power Supply
Inter-unit Control Wiring
Indoor Unit
<Type E1>
<Type E2>
Use this screw when connecting
to ground the shield for the
Inter-unit control wiring.
Remote Control
Wiring
Power
Supply
Functional ground screw (External Electronic
Expansion Valve Kit and Schedule Timer)
Inter-unit
Control Wiring
Use this screw when connecting the shield for
the Inter-unit control wiring to ground.
Power
Supply
Inter-unit
Control Wiring
Remote
Control Wiring
Functional ground screw
Sec1.indd 32
2014/11/07 10:27:56
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...