5-2
5
5
5-1. Meaning of Alarm Messages
1. Contents of the alarm display on the remote controller
ON: Blinking: OFF:
Possible cause of malfunction
Display
Wireless
remote
controller
Lamp display
Operation
Timer
Preparing
Serial commu-
nication errors
Mis-setting
Remote controller is
detecting error signal from
indoor unit
Error in receiving serial communication signal(Signal from
main indoor unit in case of group control)Outdoor system
address, indoor system address, or indoor unit individual/
main/sub setting is not set (Automatic address setting is not
completed)Auto address is not completed
E01
Error in transmitting serial communication signal
E02
Indoor unit is detecting error signal from remote controller (and system controller)
E03
Setting error
Indoor unit address setting is duplicated
E08
Remote controller setting is duplicated
E09
Indoor unit is detecting
error signaled from signal
option
Communications error between the DC fan and the driver.
E10
Error in receiving serial communications signal
E11
Setting error
Main unit duplication in simultaneous-operation multi control
(detected by outdoor unit)
E14
Indoor unit is detecting
error signaled from outdoor
unit
Error in receiving serial communications signal
E04
Error in transmitting serial communications signal
E05
Outdoor unit is detecting
error signaled from indoor
unit
Error in receiving serial communications signal (including unit
quantity verification failure)
E06
Error in transmitting serial communications signal
E07
Automatic address setting
failed
Indoor unit capacity too low
E15
Indoor unit capacity too high
E16
No indoor units connected
E20
Miswiring
Faulty connection between indoor and outdoor units or missing
phase in the outdoor unit power supply.
E22
An indoor unit detected
trouble in the signal from
another indoor unit
Error in transmitting serial communications signal
E17
Error in receiving serial communications signal
E18
Communications trouble
between units
Communications failure with MDC
E31
Mis-setting
Setting error
Indoor unit group settings error
L01
Indoor/outdoor unit type mismatch
L02
Main unit duplication in group control (detected by indoor unit)
L03
Outdoor unit address duplication (system address)
L04
Group wiring connected for independent indoor unit
L07
Address not set or group not set
L08
Indoor unit capacity not set
L09
Outdoor unit capacity not set or setting error
L10
Miswiring in group control wiring
L11
Indoor unit type setting error (capacity)
L13
Continued
Simultaneously
Simultaneously
Simultaneously
Simultaneously
SM830194-04_Single_BigPAC.indb 2
2014/11/13 18:18:54
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...