1-40
1
1
Installing Distribution Joint Kit (for Triple) (CZ-P3HPC2)
Check the system combination before installing the distribution
joints.
Three indoor units must be installed within the same room.
Use the supplied tube connectors to adjust the tube sizes of the
distribution joints.
How to Install Distribution Joints
Use the supplied distribution joints to complete refrigerant tubing
work.
Install distribution joints so that the tubes are horizontal after the
branch point.
Orientation of distribution joints
Length requirement for strainer on main distribution
tube side
Attach a straight tube 500 mm or longer to the main tubing side of
the distribution joint (for both liquid and gas tubing).
Tubing insulation
Be sure to apply thermal insulation to both the liquid and gas
tubing.
Depending on the conditions inside the ceiling, condensation may
form on the insulation material. If high temperatures and high
humidity are expected to occur inside the ceiling, add glass wool
(16 – 20 k
g
/m
3
, with a thickness of 10 mm or more) to the below
insulation materials and apply suffi cient thermal insulation.
Only the distribution joints are horizontal with
respect to the ground. The collective tubes
are vertical with respect to the ground.
The collective tube and distribution joint are
horizontal with respect to the ground.
Collective tube
<Gas tube side>
Distribution joint
Only the distribution joints are horizontal with respect
to the ground. The collective tubes are vertical with
respect to the ground.
The collective tube and distribution joint are
horizontal with respect to the ground.
Collective tube
Distribution joint
INCORRECT
Be sure to install so that the tubes are
horizontal after the branch point.
Inclination
<Liquid tube side>
Inclination
More than 500mm
Distribution joint insulation material (supplied)
• Use the supplied insulation mater
ial.
•
The supplied insulation material include only a tape for temporarily
fastening.
•
Use insulation mater
ial or other material to seal the joining lines
so that there are no gaps.
•
Use vi
nyl tape or similar means to seal and fasten the insulation
materials in place.
Seal securely with vinyl tape (4 locations)
Refrigerant tubing (fi eld supply)
Tubing insulation material (fi eld supply;
thickness of more than 10 mm) Tubing
insulation material must be able to withstand
temperatures of at least 120°C
Refrigerant tubing (fi eld supply)
More than 500mm
Sec1.indd 40
2014/11/07 10:27:59
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...