5-4. Details of Alarm Messages
Alarm Details
(1) [Alarm “P29”]
Start-up failure of the compressor (will not start up)
Related parts
• HIC PCB (Model: [U-200PE1E8, U-250PE1E8] HIC-C906VH8)
• Outdoor unit control PCB (Model: [U-200PE1E8, U-250PE1E8] CR-C906VH8P)
• Filter PCB (Model: [U-200PE1E8, U-250PE1E8] FIL-C906VH8)
Start of defect diagnosis
Is the power voltage correct?
Improve the power voltage line.
Check the following:
Check to ascertain that the power voltage is within the permissible range of 198 to 264V
for indoor unit or 342 to 456V for outdoor unit regardless of whether the compressor is
operating or not.
* Pay special attention to whether the voltage drops after compressor operations while
measuring.
Repair the wiring connectors.
Replace the outdoor
unit control PCB.
Are the wiring connector
connections OK?
Are the U / V / W
connections on the HIC
PCB and compressor
terminal OK?
Are the capacity setting
for the outdoor unit of
the outdoor unit
Are the resistance
values permissible at all
areas in HIC PCB?
Is the insulation on the
compression OK?
Has the HIC PCB been
replaced?
Has the outdoor unit
control PCB been
replaced?
Replace the compressor
Has the filter PCB
been replaced?
Repair the wiring connectors.
Repair the HIC PCB.
Repair the compressor.
Repair the HIC PCB.
Replace the filter PCB.
Correct the capacity setting for the outdoor unit.
HIC PCB side
U (CN202) pink
V (CN203) white
W (CN204) blue
As the compressors used with the U-200PE1E8 and U-250PE1E8
are different, there is a possibility that a P29 error will be triggered
if the unit's capacity settings are incorrect.
No (Abnormal resistance value)
(No problem with the resistance value)
•
Inspection Method: Remove the HIC PCB and measure the resistance at all areas.
See attached documentation.
Replace the HIC PCB if the readings are below permissible values.
(No problem with the insulation)
No (Defective insulation)
• Potential cause: PCB Insulation failure caused by the
compressor lock.
• Verification Method
Remove the wires from the connectors on the top of the
compressor. Measure the insulation resistance of the U, V and
W phases and confirm that they are 1M
Ω
or more.
Potential problems are most likely in accordance with the
following sequence when it is determined that the PCB is
trouble with an alarm P29.
1. HIC PCB
2. Outdoor unit control PCB
3. Filter PCB
Replace the relevant PCB in accordance with the diagnosis
flow.
Check the following wiring
U-200PE1E8
U-250PE1E8
HIC PCB
Outdoor unit con-
trol PCB
Filter PCB
HIC PCB
Outdoor unit con-
trol PCB
Filter PCB
HIC+
CN200 red
CN317 red
CN200 red
+
HIC-
CN201 white
CN318 white
CN201 white
-
VDCIN+
CN220 red
CN321 red
VDCIN-
CN221 red
CN322 white
HIC1(10P white)
CN100 white
CN080 white
CN100 white
CN080 white
HIC2 (yellow)
CN101 yellow 4P CN81 yellow 4P
CN101 yellow 3P CN081 yellow 4P
HIC3 (8P white)
CN102 white
CN103 white
CN102 white
CN103 white
VDC2 (2P)
CN240 yellow
CN102 white
CN240 yellow
CN102 yellow
SM830194-04_Single_BigPAC.indb 8
2014/11/13 18:18:55
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...