6-9
6
6
Setting mode 2
<Operating procedure>
(1) Press and hold the
button,
button, and
button simultaneously for 4
seconds or longer.
(2) Use the temperature setting
and
buttons to change the item
code. The item codes and setting data are shown in the table below.
(3) Use the timer time
and
buttons to change the setting data.
To confirm the changed setting data, press the
button.
(At this time, “Setting” stops blinking and remains lit.)
(4) During this mode, “Setting” is displayed, blinking. The display shows the set
outdoor unit address “System XX-YY” (System XX = System address, YY
= Address at outdoor unit sub-bus), item code number (DN value in the table below), and the setting data (6
digits).
(The setting data is displayed in 6 digits. The display changes between the first 3 digits (Fig.
A
) and the last 3
digits (Fig.
B
). When the first 3 digits are displayed, the top point of the colon is lit.)
(5) To end the setting mode, press the
button. The display returns to the normal display mode.
List of Item Codes
Item code
Parameter
80
Refrigerant type
407 = R407C 22 = R22 410 = R410A
81
Outdoor unit capacity*
0 = Disabled 22 25 28 32 36 40 45 50 56 63 71 80
90 100 112 125 140 160 180 200 224 250 280 340
355 400 450 500 560 600 630 670 710 800 840
82
Control system schedule
Do not set
83
Control system schedule
Do not set
84
3-phase or single-phase
0 = 3-phase 1 = single-phase
85
Power frequency
0 = Disabled 1 = 50Hz
86
Control system schedule
Do not set
87
Control system schedule
Do not set
88
Control system schedule
Do not set
89
Control system schedule
Do not set
8A
Control system schedule
Do not set
8b
Control system schedule
Do not set
8E
Upward fan
model only
available
Control temp. for outdoor
fan's crack prevention
Setting temperature range : -125°C ~ +125°C
Crack prevention of outdoor fan actuates when the outdoor temp.
reaches lower than the setting values.
(*) Figures represent the capacity data for each model.
A
B
(3)
(1)
(2)
(5)
Display of first 3 digits
Display of last 3 digits
(3)
(1)
(2)
(5)
80: <Refrigerant type>
A
and
B
are displayed alternately. (Example shows 000 410 (R410A).)
SM830194-04_Single_BigPAC.indb 9
2014/10/31 13:21:25
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...