2-1. Preparing for Test Run
Before attempting to start the air conditioner, check the following:
(1) All loose matter is removed from the cabinet especially
steel filings, bits of wire, and clips.
(2) The control wiring is correctly connected and all
electrical connections are tight.
(3) The protective spacers for the compressor used for
transportation have been removed.
If not, remove them now.
(4) The transportation pads for the indoor fan have been
removed. If not, remove them now.
(5) The power has been supplied to the unit for at least 5
hours before starting the compressor. The bottom of
the compressor should be warm to the touch and the
crankcase heater around the feet of the compressor
should be hot to the touch. (Fig. 2-1)
(6) Both the gas and liquid tube service valves are open.
If not, open them now. (Fig. 2-2)
Fig. 2-1
Fig. 2-2
(7) Request that the customer be present for the test run. Explain the contents of the instruction manual, and then
have the customer actually operate the system.
(8) Be sure to give the instruction manual and warranty certificate to the customer.
(9) When replacing the control PCB, be sure to make all the same settings on the new PCB as were in use before
replacement. The existing EEPROM is not changed, and is connected to the new control PCB.
2-3. Test Run Procedure
Indoor Units (Type E2, E1)
2-2. Caution
This unit may be used in a
single-type refrigerant system
where 1 outdoor unit is
connected to 1 indoor unit.
The indoor and outdoor unit
control PCB utilizes a
semiconductor memory
element (EEPROM).
The settings required for
operation were made at the
time of shipment.
Only the correct combinations
of indoor and outdoor units
can be used.
This test run section describes
primarily the procedure
when using the wired remote
controller.
(Power must be turned ON at least
5 hours before attempting test run)
Power mains switch
ON
Liquid tube
Gas tube
Fig. 2-3
YES
YES
YES
NO
NO
NO
Recheck the items to check before the test run.
Check the combination (wiring) of indoor and outdoor units.
(See 2-8-1 to 5)
(See 2-4)
Is system “single-type”?
(1 indoor unit is connected to 1 outdoor unit
and remote controller)
Is group control with
multiple outdoor units used?
Turn ON the indoor and outdoor power.
Indicate (mark) the combination number.
(See 2-8-5)
Automatic address
Set the remote controller to “test run”.
(See 2-5)
Can
operation be
started?
Return the remote controller to normal control.
Turn ON the
indoor and
outdoor power.
(Automatic
Address)
(See 2-8-3)
Setting the Outdoor
Unit System
Address
Set the outdoor
unit system
address.
(See 2-8-4)
Automatic Address
Setting
Use the remote
controller to
perform automatic
address setting.
Refer to “Table of Self-Diagnostic
Functions” to check the system.
In addition, refer to 2-8-1 to 5 and
correct any items that need to be
corrected.
Note: Check the indoor-side drainage.
(*1) Required for simultaneous-operation
multi systems and for group control.
(*1)
SM830194-04_Single_BigPAC.indb 2
2014/11/04 13:45:12
Содержание S-200PE1E8
Страница 88: ...1 82 MEMO ...
Страница 112: ...3 2 3 3 1 Outdoor Units Electric Wiring Diagram U 200PE1E8 U 250PE1E8 ...
Страница 113: ...3 3 3 Schematic Diagram U 200PE1E8 U 250PE1E8 ...
Страница 114: ...3 4 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE2E5 S 250PE2E5 Electric Wiring Diagram ...
Страница 115: ...3 5 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Electric Wiring Diagram ...
Страница 116: ...3 6 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8A Schematic Diagram ...
Страница 117: ...3 7 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Electric Wiring Diagram ...
Страница 118: ...3 8 3 3 2 Indoor Units High Static Pressure Ducted Type S 200PE1E8 Schematic Diagram ...
Страница 119: ...3 9 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Electric Wiring Diagram ...
Страница 120: ...3 10 3 3 2 Indoor Units High Static Pressure Ducted Type S 250PE1E8 Schematic Diagram ...
Страница 129: ...4 9 4 4 3 Outdoor Unit Filter PCB FIL C906VH8 ...
Страница 130: ...4 10 4 4 4 Outdoor Unit HIC Board HIC C906VH8 ...
Страница 136: ... MEMO 4 16 ...
Страница 154: ... MEMO 5 18 ...
Страница 164: ... MEMO 6 10 ...
Страница 180: ... MEMO 7 16 ...
Страница 197: ...201411 ...